Skip to main content

Kitchen Exhaust Fans

    Scope
    Scope Images
    Image
    Kitchens should be equipped with an exhaust fan that vents directly outdoors
    Scope

    Install an exhaust fan in the kitchen to exhaust steam and cooking odors to the outdoors.

    • Install the fan to vent outdoors, not into an attic, crawlspace, or space between floors.
    • Choose a smooth metal duct with the diameter specified by the fan manufacturer.
    • Install the duct with the most direct route to the outside with as few bends as possible.
    • Seal all seams and around ceiling and wall or roof penetrations with mastic or spray foam. Flash exterior surfaces as needed.
    • Install a fan that meets Rater-measured airflow codes and standards for local exhaust; meet whole-house ventilation requirements if the kitchen fan is used for whole-house mechanical ventilation. 

    See the Compliance Tab for related codes and standards requirements, and criteria to meet national programs such as DOE’s Zero Energy Ready Home programENERGY STAR Single-Family New Homes, and Indoor airPLUS.

    Description
    Description

    Regardless of what kind of ventilation system you have for the rest of the house, an exhaust fan should be installed in the kitchen to provide point or local exhaust to remove moisture and odors associated with cooking. The exhaust fan is typically located directly over the kitchen stove and is installed in a range hood or cabinet, integrated with a microwave oven, or mounted on the wall. The fan should be ducted to exhaust outside of the home, not into the attic, crawlspace, or another area inside the building. The duct serving the range hood should be made of rigid metal such as galvanized steel, stainless steel, or copper and have a smooth interior surface. It should meet the maximum length guidelines specified in the IRC (2015 IRC Table M1506.2) and the minimum diameter guidelines specified in the fan’s installation instructions; small-diameter ducts could trap grease, creating a fire hazard. It should be airtight, equipped with a back-draft damper, and independent of all other exhaust systems. 

    Recirculating fans that draw air through a filter and discharge it back into the room are not acceptable. Operable windows are a nice feature but they should not be relied on for consistent ventilation.

    Kitchen fans can be run intermittently (occupant controlled) or continuously; some fan models have multiple speed settings and can be used for either.To fulfill the local exhaust airflow requirements of the International Residential Code (IRC 2015), kitchen fans operated intermittently should have a flow rate of 100 cfm or more and fans operated continuously should have a flow rate of 25 cfm or more. Select fans that are ENERGY STAR rated, and have low sound ratings and low power draw. ENERGY STAR recommends that local kitchen exhaust fans provide ≥ 5 air changes per hour of ventilation, depending on the kitchen volume. ENERGY STAR also recommends that exhaust fans have sound ratings of ≤ 1 sone if set to run continuously or ≤ 3 sones if operating intermittently.

    Some home owners are installing commercial-scale cooking ranges with very powerful exhaust hood fans rated as high as 1200 cfm. Exhaust fan rates this high can easily backdraft a non-sealed-combustion furnace, water heater, or fireplace (Holladay 2010). Any installed exhaust fan operating in excess of 400 cfm must be provided with a makeup air system that will automatically start and operate simultaneously with the exhaust fan and will provide makeup air at a rate equivalent to the exhaust fan rate.

    Although a single-point exhaust fan such as a kitchen fan could be used to provide code-required whole-house ventilation, this strategy is not recommended. For more on whole house ventilation strategies and requirements, see the Building America Solution Center Guide Whole-House Ventilation Strategies for New Homes and Whole-House Ventilation Strategies for Existing Homes.

    Kitchen exhaust fans may be installed by the HVAC vendor or installer or by the kitchen range vendor if it is part of that system. This task should be included in the contract for the appropriate trade depending on the workflow at specific job sites.

    How to Install Exhaust Fans

    1. Determine the appropriate fan size for your application. For a continuous rate of ≥ 5 ACH, ENERGY STAR recommends selecting a fan that provides more than 5 ACH in order to pull the required amount of air. For an intermittent rate of ≥ 100 cfm, ENERGY STAR recommends selecting a fan with a rating of 150  to 200 cfm. Choose ENERGY STAR-rated fans for energy efficiency and low noise level.
      Proper sizing of kitchen exhaust fan.
      Proper sizing of kitchen exhaust fan. (Source: PNNL.)
    2. Install the fan either in the range hood, the cabinet above the stove, or on the wall above the stove. Follow the manufacturer’s instructions. The fan may also be purchased as an integrated unit that comes with a microwave oven mounted into a cabinet above the stove. Cut openings in the ceiling for the fan or exhaust duct no wider than needed to fit the fan or duct and air seal the opening with caulk or spray foam. Connect the exhaust duct to the fan box with mechanical fasteners and seal with metal tape and/or mastic. Do not use cloth-backed duct tape.
    3. Vent the kitchen fan exhaust directly to the outside, not into an attic, crawlspace, or space between floors. Use correctly sized, smooth metal duct. Seal seams and joints with mastic and/or metal tape. Install a back-draft damper that closes when the fan is not in operation. Install the duct with as few bends as possible and out of the way of other ducts or equipment in the attic. Take care not to dent or crush the duct during or after installation. The duct should be independent of other exhaust systems.
    4. Locate the exhaust duct outlet vent on the exterior of the home at least 10 feet from any air inlet. The outside termination should be covered with louvers, a screen, or a grille. The exhaust air should not be directed onto a walkway.
    5. If the fan is integrated with a microwave oven installed over the stove, install it according to the manufacturers’ instructions and 2015 IRC Section M1504.
    6. Exhaust hoods installed over domestic open-top broiler units should be made of metal and have a 1/4-inch clearance between the hood and the underside of combustible material or cabinets. The hood should extend the full width and depth of the cooktop, discharge to the outside, and have a backdraft damper, as specified in 2015 IRC Section M1505.
    7. The exhaust fan flow rate should be tested by a certified energy rater using test procedures listed in ANSI/RESNET/ICC 380-2016.
    Success
    Ensuring Success

    Visually inspect and test the kitchen exhaust fan for proper installation as follows:

    • Ensure that the fan exhausts outside, not into the attic; that it is set to exhaust, not recirculate; that any dampers on the outside termination are able to open freely; and that packing tape is removed.
    • Confirm that any openings cut in the ceiling for the fan or exhaust duct are properly air sealed and that the exhaust duct is sealed to the fan box with both mechanical fasteners and mastic and/or metal tape and caulk or spray foam.
    • Check the sone rating; ASHRAE 62.2-2007 requires 3 sones or less for intermittent (occupant-controlled) kitchen or bath exhaust fans or 1.0 sone or less for continuous fans.
    • See the Compliance tab for code and ENERGY STAR guidelines regarding flow rates and efficacy for fans used for local exhaust. See the guide Whole Building Ventilation for codes and standards related to exhaust fans used for whole-house ventilation.
    • A certified energy rater will test the fan’s operation to determine the flow rate using a flow hood, flow grid, anemometer, in accordance with test procedures listed in ANSI/RESNET/ICC 380-2016, or established by the Associated Air Barrier Council, National Environmental Balancing Bureau, or ASHRAE), or other equivalent method. Kitchen fans are typically rated by how many cubic feet per minute the fan will exhaust in a factory setting. Duct work, termination choices, and installation may decrease the measured cubic feet per minute below the factory-rated value.
    Climate
    Climate

    No climate-specific information applies.

    Training
    Right and Wrong Images
    Image
    Wrong - the CFM rating may not meet the performance specification once installed, and the sone rating is too high.
    Wrong - the CFM rating may not meet the performance specification once installed, and the sone rating is too high.
    Image
    Fan CFM rating is higher than the requirement increasing the likelihood that it will meet the performance level once installed
    Fan CFM rating is higher than the requirement increasing the likelihood that it will meet the performance level once installed
    Image
    Recirculating fan installed that does not exhaust to outside
    Recirculating fan installed that does not exhaust to outside
    Image
    Exhaust fan terminates to the outside
    Exhaust fan terminates to the outside
    Image
    Exhaust duct work and penetration to the exterior have not been sealed
    Exhaust duct work and penetration to the exterior have not been sealed
    Image
    Exhaust duct work and penetration to the exterior have been sealed with mastic
    Exhaust duct work and penetration to the exterior have been sealed with mastic
    Image
    Wrong – Overly powerful kitchen exhaust fans can backdraft other combustion appliances in the home
    Wrong – Overly powerful kitchen exhaust fans can backdraft other combustion appliances in the home
    Image
    Right – This kitchen exhaust duct is made of smooth rigid metal and the duct is mastic sealed at joints
    Right – This kitchen exhaust duct is made of smooth rigid metal and the duct is mastic sealed at joints
    Image
    Right – This kitchen exhaust fan has a damper to prevent outside air from entering when the fan is not operating
    Right – This kitchen exhaust fan has a damper to prevent outside air from entering when the fan is not operating
    Image
    Wrong – This exhaust duct extends far beyond what is needed to reach the roof; a short, straight, smooth rigid metal duct is best for exhaust ducts and exhausting to the soffit vent would be preferable.
    Wrong – This exhaust duct extends far beyond what is needed to reach the roof; a short, straight, smooth rigid metal duct is best for exhaust ducts and exhausting to the soffit vent would be preferable.
    Image
    Wrong – This kitchen exhaust is a recirculating model; kitchens should use exhaust fans that duct out through the roof to remove moisture and odors from the home
    Wrong – This kitchen exhaust is a recirculating model; kitchens should use exhaust fans that duct out through the roof to remove moisture and odors from the home
    Image
    Right – This home’s kitchen exhaust fan motor is housed in a box above the ceiling.
    Right – This home’s kitchen exhaust fan motor is housed in a box above the ceiling.
    Image
    Right – To minimize sound in the kitchen, the exhaust fan above the island-mounted stove top is located above the ceiling rather than just above the stovetop.
    Right – To minimize sound in the kitchen, the exhaust fan above the island-mounted stove top is located above the ceiling rather than just above the stovetop.
    Videos
    Compliance

    Compliance

    The Compliance tab contains both program and code information. Code language is excerpted and summarized below. For exact code language, refer to the applicable code, which may require purchase from the publisher. While we continually update our database, links may have changed since posting. Please contact our webmaster if you find broken links.

     

    ENERGY STAR Single-Family New Homes, Version 3/3.1 (Rev. 11)

    National Rater Field Checklist

    HVAC System.
    7. Dwelling Unit Mechanical Ventilation Systems (“Vent System”) 45 & Inlets In Return Duct 46
    7.4 System fan rated ≤ 3 sones if intermittent and ≤ 1 sone if continuous, or exempted. 51

    8. Local Mechanical Exhaust - In each kitchen and bathroom, a system is installed that exhausts directly to the outdoors and meets one of the following Rater-measured airflow and manufacturer-rated sound level standards: 47, 57

    National Rater Field Checklist: Local Mechanical Exhaust.
    National Rater Field Checklist: Local Mechanical Exhaust. (Source: ENERGY STAR Single-Family New Homes, Version (Rev. 11))

     

    Footnote 45) As defined by ANSI / RESNET / ICC Std. 301-2019, a Dwelling Unit Mechanical Ventilation System is a ventilation system consisting of powered ventilation equipment such as motor-driven fans and blowers and related mechanical components such as ducts, inlets, dampers, filters and associated control devices that provides dwelling-unit ventilation at a known or measured airflow rate.

    Footnote 46) Item 7.3 applies to any outdoor air inlet connected to a ducted return of the dwelling unit HVAC system, regardless of its intended purpose (e.g., for ventilation air, make-up air, combustion air). This Item does not apply to HVAC systems without a ducted return.

    Footnote 47) The Dwelling Unit Mechanical Ventilation System air flows and local exhaust air flows shall be determined and documented by a Rater using ANSI / RESNET / ICC Std. 380 including all Addenda and Normative Appendices, with new versions and Addenda implemented according to the schedule defined by the HCO that the home is being certified under.

    Footnote 51) Dwelling Unit Mechanical Ventilation System fans shall be rated for sound at no less than the airflow rate in Item 2.3 of the National HVAC Design Report. Fans exempted from this requirement include HVAC air handler fans, remote-mounted fans, and intermittent fans rated ≥ 400 CFM. To be considered for this exemption, a remote-mounted fan must be mounted outside the habitable spaces, bathrooms, toilets, and hallways and there shall be ≥ 4 ft. ductwork between the fan and intake grill. Per ASHRAE 62.2-2010, habitable spaces are intended for continual human occupancy; such space generally includes areas used for living, sleeping, dining, and cooking but does not generally include bathrooms, toilets, hallways, storage areas, closets, or utility rooms.

    Footnote 57) Continuous bathroom local mechanical exhaust fans shall be rated for sound at no less than the airflow rate in Item 8.2. Intermittent bathroom and both intermittent and continuous kitchen local mechanical exhaust fans are recommended, but not required, to be rated for sound at no less than the airflow rate in Items 8.1 and 8.2. Per ASHRAE 62.2-2010, an exhaust system is one or more fans that remove air from the building, causing outdoor air to enter by ventilation inlets or normal leakage paths through the building envelope (e.g., bath exhaust fans, range hoods, clothes dryers). Per ASHRAE 62.2-2010, a bathroom is any room containing a bathtub, shower, spa, or similar source of moisture.

    Footnote 58) An intermittent mechanical exhaust system, where provided, shall be designed to operate as needed by the occupant. Control devices shall not impede occupant control in intermittent systems.

    Footnote 59) Kitchen volume shall be determined by drawing the smallest possible rectangle on the floor plan that encompasses all cabinets, pantries, islands, peninsulas, ranges / ovens, and the kitchen exhaust fan, and multiplying by the average ceiling height for this area. In addition, the continuous kitchen exhaust rate shall be ≥ 25 CFM, per 2009 IRC Table M1507.3, regardless of the rate calculated using the kitchen volume. Cabinet volume shall be included in the kitchen volume.

    Footnote 60) Homes shall meet this Item. Alternatively, the prescriptive duct sizing requirements in Table 5.3 of ASHRAE 62.2-2010 / 2013 / 2016 are permitted to be used for kitchen exhaust fans based upon the rated airflow of the fan at 0.25 IWC. If the rated airflow is unknown, ≥ 6 in. smooth duct shall be used, with a rectangular to round duct transition as needed. Guidance to assist partners with these alternatives is available at ENERGY STAR New Homes Guidance. As an alternative to Item 8.1, homes are permitted to use a continuous kitchen exhaust rate of 25 CFM per 2009 IRC Table M1507.3, if they are either a) PHIUS+ or PHI certified, or b) provide both dwelling unit ventilation and local mechanical kitchen exhaust using a balanced system, and have a Rater-verified whole-building infiltration rate ≤ 1.0 ACH50 or ≤ 0.05 CFM50 per sq. ft. of Enclosure Area, and a Rater-verified dwelling unit compartmentalization rate ≤ 0.30 CFM50 per sq. ft. of Enclosure Area if multiple dwelling units are present in the building. ‘Enclosure Area’ is defined as the area of the surfaces that bound the volume being pressurized / depressurized during the test.

    Footnote 61) All intermittent kitchen exhaust fans must be capable of exhausting at least 100 CFM. In addition, if the fan is not part of a vented range hood or appliance-range hood combination (i.e., if the fan is not integrated with the range), then it must also be capable of exhausting ≥ 5 ACH, based on the kitchen volume.

    Please see the ENERGY STAR Single-Family New Homes Implementation Timeline for the program version and revision currently applicable in your state.

     

    DOE Zero Energy Ready Home (Revision 07)

    Exhibit 1 Mandatory Requirements.
    Exhibit 1, Item 1) Certified under the ENERGY STAR Qualified Homes Program or the ENERGY STAR Multifamily New Construction Program.
    Exhibit 1, Item 6) Certified under EPA Indoor airPLUS

     

    2009 International Energy Conservation Code (IECC)

    Section 403.5 Mechanical ventilation (Mandatory). Automatic or gravity dampers are installed on all outdoor air intakes and exhausts.

    2012, 2015, 2018, and 2021 International Energy Conservation Code (IECC)

    Section R403.5 (R403.6 in 2015, 2018, and 2021 IECC) Mechanical ventilation shall meet the requirements of the International Residential Code or the International Mechanical Code. Automatic or gravity dampers are installed on all outdoor air intakes and exhausts. Table R403.5.1 (R403.6.1 in 2015 and 2018 IECC and R403.6.2 in 2021 IECC) Mechanical Ventilation System Fan Efficacy for range hood and in-line fans shall be at least 2.8 cfm/watt.

    Retrofit:  2009, 2012, 2015, 2018, and 2021 IECC

    Section R101.4.3 (in 2009 and 2012). Additions, alterations, renovations, or repairs shall conform to the provisions of this code, without requiring the unaltered portions of the existing building to comply with this code. (See code for additional requirements and exceptions.)

    Chapter 5 (in 2015, 2018, 2021). The provisions of this chapter shall control the alteration, repair, addition, and change of occupancy of existing buildings and structures.

     

    2009 International Residential Code (IRC)

    Section M1507.3 Ventilation rate. Kitchen fans should have an exhaust rate of 100 cfm intermittent or 25 cfm continuous.

    2012 IRC

    M1503 Range Hoods  Range hoods should discharge to the outdoors through a metal duct made of galvanized steel, stainless steel, or copper; with a smooth interior surface that is air tight and equipped with a back draft damper. The duct should be independent of other exhaust systems and should not terminate in an attic, crawl space, or other inside space. Exhaust fans capable of exhausting ≥ 400 cfm should be mechanically or naturally provided with makeup air at a rate equal to the exhaust air rate. The makeup air system should have a gravity or electrically operated damper that automatically opens when the system operates and that is accessible for inspection.

    M1504 Microwaves installed over a listed and labeled cooking appliance shall conform to the terms of the microwave’s listing and label and manufacturer’s installation instruction. The microwave oven shall also conform to UL 923.

    M1505 Open-top broiler units should have a min. 28-gauge metal exhaust hood with ¼-inch clearance between the hood and the underside of combustible material or cabinets. The hood should be at least as wide as the broiler, and extend over the entire unit, discharge to the outdoors, and be equipped with a back draft damper.

    M1506  Exhaust opening should terminate at least 3 feet from property lines, 3 feet from operable and non-operable openings into the building, and 10 feet from mechanical air intakes, except where the opening is located 3 feet above the air intake.

    M1507 The whole-house mechanical ventilation system shall consist of one or more supply or exhaust fans, or a combination of such and associated ducts and controls. Local exhaust or supply fans are permitted to serve as such a system. Outdoor air ducts connected to the return side of an air handler shall be considered as providing supply ventilation. The whole-house mechanical ventilation system shall be provided with controls that enable manual override.

    The whole house mechanical ventilation system shall provide outdoor air at a rate equivalent to the minimum rates shown in Tables M1507.3.3(1) and M1507.3.3(2), which are based on the home's floor area.

    Local exhaust rates (per Table M1507.4) Kitchen fans should have an exhaust rate of 100 cfm if operated intermittently or 25 cfm if operated continuously.

    2015 IRC

    Same as 2012. Duct length and diameters are specified in Table M1506.2 and are based on the fan flow rate, which should be in accordance with ANSIE/AMCA 210-ANSIE/ASHRAE 51.

    2018 and 2021 IRC

    Section M1503 Domestic Cooking Exhaust Equipment describes requirements for exhaust equipment associated with kitchens and kitchen appliances. Overhead range hoods and downdraft exhaust equipment with integral fans shall comply with UL507. M1503.3 Exhaust discharge states that domestic cooking exhaust shall discharge tot he outdoors through a duct. The duct shall have a smooth interior surface, shall be airtight, shall be equipped with a backdraft damper and shall be independent of all other exhaust systems.

    Retrofit:  2009, 2012, 2015, 2018, and 2021 IRC

    Section R102.7.1 Additions, alterations, or repairs. Additions, alterations, renovations, or repairs shall conform to the provisions of this code, without requiring the unaltered portions of the existing building to comply with the requirements of this code, unless otherwise stated. (See code for additional requirements and exceptions.)

    Appendix J regulates the repair, renovation, alteration, and reconstruction of existing buildings and is intended to encourage their continued safe use.

     

    American Society of Heating, Refrigeration and Air Conditioning Engineers (ASHRAE) 62.2-2010, ASHRAE 62.2-2013, and ASHRAE 62.2-2016

    ASHRAE Standard 62.2 Ventilation for Acceptable Indoor Air Quality in Low-Rise Residential Buildings (available for purchase at link above). The standard provides minimum requirements for mechanical and natural ventilation systems intended to provide acceptable indoor air quality in low-rise residential buildings.

     

    American National Standards Institute (ANSI)/Residential Energy Services Network (RESNET)/International Code Council (ICC) 380-2016

    Standard for testing Airtightness of Building Enclosures, Airtightness of Heating and Cooling Air Distribution Systems, and Airflow of Mechanical Ventilation Systems. Section 5.1 defines procedures for measuring the airflow of a mechanical ventilation system including a powered flow hood, an airflow resistance device, or a passive flow hood.

    Retrofit
    Existing Homes

    SCOPE

    Install or replace the kitchen exhaust fan, if the kitchen currently lacks an exhaust fan or the existing fan is a recirculating model or has insufficient draw, as determined by occupant experience or through fan testing by a home energy rater.

    If the current kitchen fan exhausts into the attic, crawlspace, or between floors, replace the duct with one that exhausts to the outside.

    See the assessment guide, Pre-Retrofit Assessment of Attics, Ceilings, and Roofs.

    For more on exhaust fan ventilation, see the U.S. Department of Energy’s Standard Work Specifications.

    See the Scope tab for additional job specifications.

    DESCRIPTION

    Installation of a new kitchen exhaust fan is warranted if the kitchen currently has no exhaust fan or if the existing fan is a recirculating model that does not vent to the outside. Other reasons to replace the fan include noise or moisture complaints by the homeowner or fan testing as part of a home energy audit that reveals that the fan has insufficient draw. A less common reason to replace the fan is if it has too much draw. Commercial-grade cook tops that are installed in some home kitchen remodels often come with overly powerful exhaust hood fans that have exhaust flow rates far above what is required by code. If testing by a home energy rater reveals that the exhaust fan is, or could potentially, backdraft the fireplace or other combustion appliances in the home, and it is difficult to find wall space to install a vent large enough to supply a sufficient amount of makeup air to the kitchen, a less expensive option may be to replace the exhaust fan within the range hood with a fan that exhausts at a rate closer to what is required by code. Follow the installation instructions provided in the Description tab.

    COMPLIANCE 

    See Compliance tab. 

    More

    More Info.

    Access to some references may require purchase from the publisher. While we continually update our database, links may have changed since posting. Please contact our webmaster if you find broken links.

    Case Studies
    References and Resources*
    Author(s)
    Holladay Martin
    Organization(s)
    Green Building Advisor
    Publication Date
    Description
    If your kitchen has a powerful exhaust fan, it may be pulling air down your chimney or water-heater flue.
    *For non-dated media, such as websites, the date listed is the date accessed.
    Contributors to this Guide

    The following authors and organizations contributed to the content in this Guide.

    Sales
    Building Science Measures
    Building Science-to-Sales Translator

    Kitchen Exhaust Fan = Kitchen Odor and Moisture Control Fan

    Image(s)
    Technical Description

    Kitchen odor and moisture control fans use high-efficiency range hoods ducted to vent outdoors to remove odors and moisture from cooking. Recirculating type exhaust fans only filter the air and return it to the kitchen with much less effective and persistent health benefits. ENERGY STAR-rated exhaust fans meet performance criteria for energy efficiency and sound levels.

    Kitchen Odor and Moisture Control Fan
    Sales Message

    Kitchen odor and moisture control fans help ensure adequate exhaust when cooking. What this means to you is some of the most significant contaminants in homes are effectively removed right at their source. Wouldn’t you agree protecting health is too important to ignore in new homes?

    Last Updated

    Did you find this information helpful?

    If you have questions and/or would like a reply to this feedback, please include your e-mail address in the message.
    This question is for testing whether or not you are a human visitor and to prevent automated spam submissions.