Skip to main content

Scope

Diagram of buried ducts
Diagram of buried ducts

When HVAC ducts are installed in a vented attic in a dry climate, bury the ducts in attic insulation to protect them from temperature extremes in the unconditioned attic space.

  • Install ductwork so that it is in direct contact with (i.e., laying on) the ceiling and/or truss lower cords.
  • Use metal, flex, or fiber board ducts that are insulated to code. The duct insulation should include a vapor barrier cover.
  • Mechanically fasten and mastic-seal all duct connections.
  • Test total duct leakage. Add additional sealant if necessary.
  • Install loose-fill insulation to cover the ducts and the attic floor to meet or exceed the code-required R value for attic insulation.
  • If using this technique in a humid or marine climate, the ducts must be encapsulated with spray foam before installing the blown insulation. See Encapsulated Ducts and Ducts Buried in Attic Insulation & Encapsulated for more information.
  • This technique fulfills the DOE Zero Energy Ready Home program requirement that ducts be installed in conditioned space.

See the Compliance Tab for links to related codes and standards and voluntary federal energy-efficiency program requirements.

Description

For homes with ducted heating and cooling systems, the best place to locate the duct system from an HVAC performance standpoint is within the conditioned space of the home, either in dropped ceilings, or between floors, or in a sealed and insulated basement, crawlspace, or attic. If the ducts must be located within a vented attic, one option for protecting the ducts and helping to minimize heat transfer between ducts and the unconditioned attic is to lay the ducts on the attic floor and cover them with the same blown insulation that is used to cover the attic floor. The ductwork should be installed so that it is in direct contact with the ceiling and/or truss lower cords. Metal, flex, or fiber board ducts can be used. The ducts should be covered with R-8 or higher duct insulation and the duct insulation should include a vapor barrier cover. All duct connections should be mechanically fastened and mastic-sealed. The ducts should be tested for total duct leakage and any leaks should be sealed. Once these preparations are made, the ducts can be buried in loose-fill insulation (typically blown fiberglass or cellulose) at the same time that the attic floor is being insulated. The insulation levels should meet or exceed the code-required R value for attic insulation. Figure 1 shows a duct that is partially, fully, or deeply buried in blown attic insulation.

If using this technique in the humid or marine climates, the ducts must be encapsulated with spray foam before installing the blown insulation. See Encapsulated Ducts and Ducts Buried in Attic Insulation & Encapsulated for more information.

Buried ducts are laid on the floor of a vented attic then covered with spray foam and blown attic floor insulation
Buried ducts are laid on the floor of a vented attic then covered with spray foam and blown attic floor insulation
Buried ducts are laid on the floor of a vented attic then covered with spray foam and blown attic floor insulation
Source
Table 1. Effective R-Values of Buried Ducts at Three Attic and Duct Insulation Levels. (Source: Steven Winter Associates.)

The effective R-value of a buried duct installation depends on the size of the ducts, the R-value of the duct insulation, and the depth of the loose-fill insulation. Table 1 shows effective R-values for 8-inch round ducts at three attic insulation levels and three duct insulation levels (R-4.2, R-6, and R-8).

Effective R-Values for Buried Ducts at Three Levels of Attic and Duct Insulation.
Table 1. Effective R-Values of Buried Ducts at Three Attic and Duct Insulation Levels. (Source: Steven Winter Associates.)

Typically, the duct design will consist of one or more main supply trunk(s) and perpendicular duct branches serving each of the ceiling registers. If the trunk is perpendicular to the truss bottom chords, then the duct branches can be parallel and rest directly on ceiling. If the main truck is placed parallel to the ceiling supports, then the branches will need to run perpendicular to and rest on top of the truss chords. Either configuration will work, giving the designer the flexibility to select whichever method works best for a particular circumstance. In every case, a compact, low-profile layout should be a primary goal.

How to Install Buried Ducts After Ceiling is in Place

  1. Install ceiling gypsum board prior to installing buried ducts (Figure 2).
Ceiling gypsum board has been installed
Ceiling gypsum board has been installed
Ceiling gypsum board has been installed
Source
Figure 2. Ceiling gypsum board, HVAC ducts, and other services have been installed but not attic insulation. (Source: Steven Winter Associates.)
  1. Install ductwork across lower truss cords or rafters or resting on the ceiling drywall. Install insulated ducts that have a minimum of R-8 duct insulation and in integral vapor barrier. Install the ductwork in accordance with a low-profile compact duct design (Figure 3).

    This duct is insulated with a minimum of R-8 insulation.
    Figure 3. This duct is insulated with a minimum of R-8 insulation. (Source: Steven Winter Associates.)
  2. Properly fasten and seal ducts at all connections. To attach flex duct, pull back outer liner, fasten inner liner over collar with tool-tightened tension tie, mastic seal the connection. Pull insulation and outer liner over the joint and seal to attached duct or boot with mastic or foil tape. The outer liner should not be attached with a tie as shown here but should be connected with mastic or foil tape to avoid compressing the insulation.
The inner liner of the flex duct is fastened to the collar with a tension tie, the connection is sealed with mastic, then the outer layer is pulled over and sealed with mastic or foil tape (Steven Winter Associates 2013).
The inner liner of the flex duct is fastened to the collar with a tension tie, the connection is sealed with mastic, then the outer layer is pulled over and sealed with mastic or foil tape (Steven Winter Associates 2013).
The inner liner of the flex duct is fastened to the collar with a tension tie, the connection is sealed with mastic, then the outer layer is pulled over and sealed with mastic or foil tape (Steven Winter Associates 2013).
Source
Figure 4. The inner liner of the flex duct is fastened to the collar with a tension tie, the connection is sealed with mastic, then the outer layer is pulled over and sealed with mastic or foil tape. (Source: Steven Winter Associates.)
  1. Test total duct leakage with a duct blaster to ensure that the ducts have been adequately sealed (total duct leakage < 3 cfm25 per 100 ft2 of conditioned space) (Figure 5).

    Total duct leakage test.
    Figure 5. A duct blaster is used to test total duct leakage. (Source: Steven Winter Associates.)
  2. Air-seal the ceiling plane penetrations, including sealing the duct register boots to the gypsum board ceiling using canned spray foam (Figure 6).
Duct boots and other ceiling penetrations are air-sealed using spray foam
Duct boots and other ceiling penetrations are air-sealed using spray foam
Duct boots and other ceiling penetrations are air-sealed using spray foam
Source
Figure 6. Duct boots and other ceiling penetrations are air-sealed using spray foam. (Source: Steven Winter Associates.)
  1. Install loose-fill insulation to the specified depth, and verify that the ducts are covered to the level desired (Figure 7).

    Loose fill installed.
    Figure 7. Loose-fill attic insulation is installed to the specified depth. (Source: Steven Winter Associates.)

    strong>How to Install Buried Ducts before the Ceiling Is in Place

    1.  
      1. Install ductwork across lower truss cords or rafters. Install insulated ducts that have a minimum of R-8 duct insulation and an integral vapor barrier. Install the ductwork in accordance with a low-profile compact duct design. Where ducts are running parallel to ceiling framing, provide temporary blocking to hang ducts approximately 2 inches above the ceiling plane to allow for the thickness of the spray foam. (Figure 8).

        Ducts installed before ceiling.
        Figure 8. These ducts were installed before the ceiling drywall was installed. Ducts are supported by temporary strapping across the lower truss cords. (Source: Steven Winter Associates.)
      2. Connect, seal, and test ducts as described above in Steps 3 and 4.
      3. Install ceiling gypsum board after installing ducts.
      4. Air seal ceiling plane and and install attic floor insulation as described in Steps 5 and 6 above.

Ensuring Success

Buried ducts can be used in dry climates. For humid and marine climates, ducts should be encapsulated in at least 1.5 inches of closed-cell spray foam before burying in blown insulation. As with all advanced systems, the key to optimal implementation lies with the initial planning. To accommodate a buried ducts strategy, the designer must also consider how best to incorporate a low-profile design, where the system layout is specifically designed to place ducts as low as practical to allow ductwork to hug the drywall ceiling where possible. Other best-practice measures, which assist in achieving the desired low-profile layout, should be incorporated into the building, including compact HVAC distribution and right-sized HVAC sizing. Specifically, smaller ducts (lower duct height) and inboard registers (shorter duct runs) mean that there is less ductwork to bury.

Return trunks and branches could be treated in the same manner; however, to keep the HVAC distribution system at a minimum, while simultaneously providing good comfort and proper airflow, the use of central returns is recommended. Return air paths from bedrooms and other spaces can be accommodated by low-profile jump ducts.

Region

Buried & encapsulated ducts may be installed in all climate zones, including moist (A) and marine (C) climate zones. The ccSPF insulation mitigates condensation concerns in these climates. 

The map in Figure 1 shows the climate zones for states that have adopted energy codes equivalent to the International Energy Conservation Code (IECC) 2009, 12, 15, and 18. The map in Figure 2 shows the climate zones for states that have adopted energy codes equivalent to the IECC 2021. Climate zone-specific requirements specified in the IECC are shown in the Compliance Tab of this guide. 
 

IECC climate zone map
IECC climate zone map
IECC climate zone map
Source
Author(s)
International Code Council
Organization(s)
ICC
Description

2012 edition of code establishing a baseline for energy efficiency by setting performance standards for the building envelope (defined as the boundary that separates heated/cooled air from unconditioned, outside air), mechanical systems, lighting systems and service water heating systems in homes and commercial businesses.

Figure 1. Climate Zone Map from IECC 2009, 12, 15, and 18. (Source: 2012 IECC)
Climate Zone Map from IECC 2021
Climate Zone Map from IECC 2021
Climate Zone Map from IECC 2021
Source
Author(s)
International Code Council
Organization(s)
ICC
Description

2021 edition of code establishing a baseline for energy efficiency by setting performance standards for the building envelope (defined as the boundary that separates heated/cooled air from unconditioned, outside air), mechanical systems, lighting systems and service water heating systems in homes and commercial businesses.

Figure 2. Climate Zone Map from IECC 2021. (Source: 2021 IECC)

Training

Right and Wrong Images

Right: Ducts are completely buried beneath insulation to the depth specified in the plans
Right: Ducts are completely buried beneath insulation to the depth specified in the plans
Right: Ducts are completely buried beneath insulation to the depth specified in the plans
Source
Wrong: Ducts are not laid across the lower truss cords or ceiling, but are hung from the rafters by straps. As a result, ductwork is not buried
Wrong: Ducts are not laid across the lower truss cords or ceiling, but are hung from the rafters by straps. As a result, ductwork is not buried
Wrong: Ducts are not laid across the lower truss cords or ceiling, but are hung from the rafters by straps. As a result, ductwork is not buried
Source
Wrong: Duct is hung between truss members by strapping and not buried
Wrong: Duct is hung between truss members by strapping and not buried
Wrong: Duct is hung between truss members by strapping and not buried
Source
Right: Ductwork is installed in direct contact with lower truss cords. In this picture the main trunk is laying on the truss cords and branch ducts are temporarily held with strapping across truss cords. Ducts are well sealed with mastic
Right: Ductwork is installed in direct contact with lower truss cords. In this picture the main trunk is laying on the truss cords and branch ducts are temporarily held with strapping across truss cords. Ducts are well sealed with mastic
Right: Ductwork is installed in direct contact with lower truss cords. In this picture the main trunk is laying on the truss cords and branch ducts are temporarily held with strapping across truss cords. Ducts are well sealed with mastic
Source
Wrong: Ducts are held from the rafters with strapping and a large beam prevents ducts from properly lying on the ceiling plane
Wrong: Ducts are held from the rafters with strapping and a large beam prevents ducts from properly lying on the ceiling plane
Wrong: Ducts are held from the rafters with strapping and a large beam prevents ducts from properly lying on the ceiling plane
Source
Right: Side-entry boots are used to keep ductwork close to the ceiling
Right: Side-entry boots are used to keep ductwork close to the ceiling
Right: Side-entry boots are used to keep ductwork close to the ceiling
Source
Wrong: Ducts are held above the ceiling plane with strapping to provide a good angle into top-entry boots. Once the ceiling insulation is added, this duct will protrude from the ceiling insulation and will not be buried
Wrong: Ducts are held above the ceiling plane with strapping to provide a good angle into top-entry boots. Once the ceiling insulation is added, this duct will protrude from the ceiling insulation and will not be buried
Wrong: Ducts are held above the ceiling plane with strapping to provide a good angle into top-entry boots. Once the ceiling insulation is added, this duct will protrude from the ceiling insulation and will not be buried
Source
Right: ductwork is fully encapsulated with ccSPF prior to ceiling installation and burial
Right: ductwork is fully encapsulated with ccSPF prior to ceiling installation and burial
Right: ductwork is fully encapsulated with ccSPF prior to ceiling installation and burial
Source
Wrong: Ductwork is not fully encapsulated with ccSPF insulation. The duct jacket is still fully visible at sections of the duct
Wrong: Ductwork is not fully encapsulated with ccSPF insulation. The duct jacket is still fully visible at sections of the duct
Wrong: Ductwork is not fully encapsulated with ccSPF insulation. The duct jacket is still fully visible at sections of the duct
Source
Wrong- A tie strap should not be used over the duct outer liner because it can compress the insulation. Tuck in the fibrous insulation and seal the outer liner to the connecting duct with mastic or foil tape (Steven Winter Associates 2013).
Wrong- A tie strap should not be used over the duct outer liner because it can compress the insulation. Tuck in the fibrous insulation and seal the outer liner to the connecting duct with mastic or foil tape (Steven Winter Associates 2013).
Wrong- A tie strap should not be used over the duct outer liner because it can compress the insulation. Tuck in the fibrous insulation and seal the outer liner to the connecting duct with mastic or foil tape (Steven Winter Associates 2013).
Source

Presentations

Author(s)
Zoeller
·
Organization(s)
Steven Winter Associates
Description
Presentation with technical training covering several possible approaches to locating ducts within the home’s air and thermal barriers, and then dig into design considerations and details for the spray foam encapsulation approach.

Retrofit

SCOPE

In existing homes with vented attics and HVAC ducts that are installed on the attic floor, bury ducts in blown attic insulation when adding or increasing attic insulation.

Before adding blown insulation,

  • Inspect and test the ducts for missing or torn duct insulation; sagging, crushed. or excess flex duct; disconnected or leaking ducts.
  • Repair and air seal ducts as needed before installing spray foam insulation.
  • See the following for more information about insulating and air sealing metal, flex, or fiber board ducts.
  • Flex duct runs should be pulled taut to reduce internal airflow friction. See the following guides to remedy installation problems prior to sealing or adding insulation to an existing flex duct system:

If ducts are hung in attic rather than laying on the attic floor, see the guide Encapsulated Ducts.

For more information, view the U.S. Department of Energy’s Standard Work Specifications regarding ducts.

Also see the Solution Center guide Pre-Retrofit Site Assessment of Attics, Ceilings and Roofs.

DESCRIPTION

Make any needed repairs as described above then follow installation guidance for new homes in the Description tab.

COMPLIANCE 

See Compliance tab. 

More Info

Case Studies

Publication Date
·
Author(s)
Pacific Northwest National Laboratory,
Steven Winter Associates
·
Organization(s)
PNNL,
CARB,
SWA
Description
Case study describing a DOE Building America Top Innovation on HVAC ducts located in vented attics that are encapsulated in foam and buried in attic insulation.

References and Resources

Publication Date
·
Author(s)
National Renewable Energy Laboratory,
U.S. Department of Energy
·
Organization(s)
NREL,
DOE
Description
Fact sheet describing best strategies to bring ductwork on single-story homes with a slab-on-grade foundation in hot, dry climates into the conditioned envelope of the home intending to highlight the pros and cons of multiple ductwork integration strategies, including traditional duct systems in...

*For non-dated media, such as websites, the date listed is the date accessed.

Contributors to this Guide

The following authors and organizations contributed to the content in this Guide.

Steven Winter Associates, lead for the Consortium for Advanced Residential Buildings (CARB), a DOE Building America Research Team

Sales

Building Science-to-Sales Translator

Vented Attics with Buried HVAC Ducts

Image(s)

Technical Description

Comfort systems installed in vented attics work much better when they are buried in insulation. Vented attics can reach extreme temperatures. Deeply burying the ducts in the attic's insulation provides significant protection from these harsh conditions. The ducts need to be tightly sealed to ensure optimum performance.

Last Updated

Questions? Comments? Contact our webmaster.

Disclaimer

This content is a work created with funding provided by the United States Department of Energy under Contract no DE-AC05-076RL01830 for the operation of Pacific Northwest National Laboratory. The information and guidance provided by Pacific Northwest National Laboratory (PNNL) in the content are intended solely for educational purposes only and do not constitute formal training or certification. It is provided with the explicit understanding that neither the United States Government nor the United States Department of Energy, nor the Contractor, nor any or their employees, nor any jurisdiction or organization that has cooperated in the development of these materials, makes any warranty, express or implied, or assumes any legal liability or responsibility for the accuracy, completeness, or usefulness or any information, apparatus, product, software, or process disclosed, or represents that its use would not infringe privately owned rights. Reference herein to any specific commercial product, process, or service by trade name, trademark, manufacturer, or otherwise does not constitute or imply its endorsement, recommendation, or favoring by the United States Government or any agency thereof, or Battelle Memorial Institute. The views and opinions of authors expressed herein do not necessarily state or reflect those of the United States Government or any agency thereof. Viewers assumes full responsibility for all actions that they may take from information provided in this content including ensuring the safety, code compliance, and proper functionality of any products they choose to install. Installation and use of such products should be performed in accordance with local regulations and manufacturer instructions.