Floor Above Garage

Scope

Air seal the floor above a garage when there is living space above the garage and make sure floor insulation is in full contact with the underside of the subfloor.
Air seal the floor above a garage when there is living space above the garage and make sure floor insulation is in full contact with the underside of the subfloor.

Air seal the floor above a garage when there is living space above the garage and make sure floor insulation is in full contact with the underside of the subfloor.

  • Seal all seams, gaps, and holes in the subfloor air barrier with caulk or foam. 
  • Air seal rim joists and any holes in the top plate of the garage walls.
  • Install insulation without misalignments, compressions, gaps, or voids. 
  • Install supports to keep insulation in permanent contact with the air barrier above, for example, metal staves for batt insulation or netting for blown insulation.
  • If spray foam insulation is used for the floor cavity insulation, the spray foam can serve as the air barrier if it is at least 5.5 inches thick if open-cell or at least 1.5 inches thick if closed-cell spray foam insulation. 
  • Consider a combination of spray foam and fibrous insulation to thoroughly air seal and meet insulation R-value requirements.

See the Compliance Tab for related codes and standards requirements, and criteria to meet national programs such as DOE’s Zero Energy Ready Home program, ENERGY STAR Certified Homes, and Indoor airPLUS.

Description

Even when a garage is attached to the home, it is still outside the thermal envelope of the home, so the walls and ceiling separating it from the rest of the home must be insulated and air sealed just like any exterior walls or floors above unconditioned space. For the Insulation installed in the floor above a garage to be effective, it must be in full contact (continuous alignment) with the subfloor above and with the rim joists on all sides and any seams or holes in the subfloor and rim joists must be sealed. This air sealing provides a continuous air barrier which serves two purposes: it keeps wind from blowing through the insulation and robbing it of its thermal value and, even more importantly, it prevents garage air pollutants like car exhaust and chemical fumes from migrating into the home (EPA 2008).

When the insulation is not in contact with the subfloor (as shown in Figure 1), it creates space for air to flow, either from unsealed exterior walls or from convective loops of air currents. The moving air pulls heat from the floor system, robbing the insulation of its effectiveness and causing cold floors above. The solution to eliminating these thermal short circuits is two-fold: First, completely air seal the floor system, paying particular attention to sealing the band/rim joist area to create a continuous air barrier. Second, install the ceiling insulation in full alignment (continuous contact) with this air barrier (EPA 2008).

 

misaligned floor insulation

Figure 1 -  When insulation is not in contact with the subfloor above, moving air has the opportunity to wash over the insulation, degrading its insulating value. Reference

 

Infiltration through band joist

Figure 2 - The joints between the top and bottom plates, rim joist, and subfloor in platform framing present many opportunities for air infiltration.  Reference

 

How to Insulate and Air Seal the Floor above an Attached Garage

  1. Install a subfloor that can serve as a continuous air barrier between the garage and the rooms above. In most cases, this air barrier will be plywood or OSB floor sheathing. Install the subfloor sheathing panels according to APA Sturd-I-Floor recommendations, which includes the following (APA 2011):
  • Install subfloor in panel widths that align with the framing (typically 16-, 20-, or 24-inches on-center).
  • Stagger subfloor panel end joints.
  • Use tongue-and-groove subfloor panels or install blocking beneath panel joints.
  • Apply construction adhesive or caulk at panel seams and between subfloor panel and framing members.

Subfloor as air barrier

Figure 3 - Seams in the subfloor are sealed with construction adhesive so that the subfloor can serve as an air barrier separating the garage from the living space above. Reference

2.   Air seal the band and rim joists and any penetrations.

  • Block off any open floor joists running from the garage ceiling to under other parts of the home to prevent the infiltration of airborne pollutants (EPA 2008). See the guide Garage Rim/Band Joist Adjoining Conditioned Space for more information. Use an air barrier material such as plywood, sheathing, rigid foam, or OSB (see Figure 4). Do not use batt insulation for air sealing. 

 sealed blocking

Figure 4 - Use plywood, OSB, or another rigid material to block floor joists that connect the garage ceiling to the rest of the house. Reference

  • If I-joists are used, the blocking material must be cut to fit the shape. This can be done with filler strips as shown in Figure 4. Or, the corners of the blocking may be cut to fit around the I-joist flanges, as shown in Figure 5. 
  • Seal the edges of the blocking with a one- or two-part foam sealant or caulk. Foam sealant will work better (and last longer) than caulk. Spray foam can be used to cover the whole air barrier (Figure 6) to fill small voids and cracks to effectively stop air flow, while also providing additional R-value (DOE 2012).

Filler Blocking

Figure 5 - Cut the air barrier material to fit the shape of the joist bay. Reference

 

Spray foam at band joist

Figure 6 - Spray foam effectively fills the irregularities around I-joists while providing a tight air seal and insulation in one step. Reference

   3.  Install insulation in the floor joists.

  • Insulation should be fully "aligned" with the air barrier, i.e., in full contact with the subfloor above. There can be no gaps between the insulation and the sheathing above it (EPA 2011).
  • Batt insulation should fit tightly between the floor joists but avoid gaps, compressions, or voids. Batts should be fully lofted (not crammed or compressed into the space, see Figure 6). Batts should be cut lengthwise to fit narrow joist bays, and split to fit neatly around electrical wiring running across joist bays. See the guide Insulation Installation Achieves RESNET Grade 1 for more on quality installation.

Correctly insulated floor

Figure 7 - Unfaced batt insulation completely fills the joist cavities and will maintain contact with the subfloor above once ceiling drywall is installed.  Reference

  • Blown-in fiberglass or cellulose is especially effective for insulating garage ceilings when webbed floor trusses are used because it can fill in voids around the trusses. First install netting or the ceiling drywall to hold the insulation. Install the blown-in insulation to the correct volume and density to maintain contact with the subfloor above and prevent settling. Confirm with the insulation manufacturer or installer that the drywall will hold the weight of the insulation needed (EPA 2008).
  • Spray foam insulation can be used to insulate the floor above a garage as well as the band joist. Spray foam provides high R-value and a continuous air barrier in one labor-saving application. To qualify as an air barrier, open-cell spray foam must have a finished thickness 5.5 inches and closed-cell spray foam must have a finished thickness 1.5 inches (EPA 2011).

Spray foam over the garage

Figure 8 - Spray foam is installed over the garage to provide both air sealing and insulation in one application. Reference

   4.  Support insulation.

  • Batt insulation must be installed to sufficient depth that it will stay in contact with the subfloor above when drywall is installed below it. If drywall will not be installed, install metal staves or mechanically fastened wire to keep batts in continuous contact with the subfloor above.
  • Blown insulation must be installed at sufficient depth and density to completely fill the floor joist cavities from the ceiling drywall to the subfloor above.
  • Spray foam alone requires no addtional support. If spray foam is used in combination with batt or blown insulation, the batt or blown insulation must be supported or installed at sufficient depth to fill the ceiling cavities.

Insulation support

Figure 9 - Use metal stays or wire to keep insulation in full contact with the subfloor above it. Reference

Ensuring Success

Blower door testing conducted as part of whole-house energy performance testing, may help indicate whether air leakage at the floor has been successfully sealed. Infrared imaging with an infrared camera may be used to determine air leakage at the floor over a garage. For best results, scan twice. First, scan under static conditions before blower door testing has been conducted. This will allow the technician to evaluate the integrity of insulation behind the drywall if the garage ceiling has been finished. Conduct a second scan with the blower door running in depressurization mode and the door between the house and the garage open. This will demonstrate the integrity of the air barrier, showing where air leakage has infiltrated the framing and seeped through insulation. With the blower door pressurizing, the garage door closed and the door to the house open, check for air leaks in the floor and near the rim joist with a smoke pencil. A smoke trail moving away from the smoke pencil indicates a leak to the unconditioned space that should be sealed.

Climate

In cold climates, avoid installing plumbing in floors over garages because the pipes could freeze.

Floors above garage cold climate 

 Reference

 

Install insulation in amounts that meet or exceed code-required levels for your climate zone. See for example Table R402.1.1 in the 2009 or 2012 International Energy Conservation Code (2009 IECC, 2012 IECC) or Table R402.1.2 in the 2015 IECC)

ENERGY STAR Certified Homes 

ENERGY STAR Certified Homes (Ver. 3/3.1 Ver 08) Rater Field Checklist, a complete air barrier that is fully aligned with insulation is installed at the exterior vertical surface of floor insulation in all climate zones and, if over unconditioned space, also at the interior horizontal surface.
 

DOE Zero Energy Ready Home

DOE Zero Energy Ready Home (Rev 05) Exhibit 2:  Infiltration: Climate Zones 1-2: 3 ACH 50; Zones 3-4: 2.5 ACH50; Zones 5-7: 2 ACH50; Zone 8: 1.5 ACH50. Building envelope leakage shall be determined by an approved verifier using a RESNET-approved testing protocol.

 

climate zone map

International Energy Conservation Code (IECC) Climate Regions

Training

Right and Wrong Images

Presentations

  1. Presentation: Floor Above Garage
    (6 MB)
    Author(s): Steve Easley & Associates
    Organization(s): Steve Easley & Associates

Videos

  1. Floor Above Garage
    Publication Date: July, 2015
    Courtesy Of: Risinger Homes

    Video describing best practices for air sealing floors above garages.

CAD Images

Compliance

ENERGY STAR Certified Homes

ENERGY STAR Certified Homes (Version 3/3.1, Revision 08), Rater Field Checklist, Thermal Enclosure System 

2. Fully-Aligned Air Barriers.5 At each insulated location below, a complete air barrier is provided that is fully aligned as follows: 

Floors: At exterior vertical surface of floor insulation in all climate zones and, if over unconditioned space, also at interior horizontal surface including supports to ensure alignment. See Footnotes 10 & 11 for alternatives.9, 10, 11

2.6 Floors above garages, floors above unconditioned basements or crawlspaces, and cantilevered floors 

Footnotes:

(5) For purposes of this Checklist, an air barrier is defined as any durable solid material that blocks air flow between conditioned space and unconditioned space, including necessary sealing to block excessive air flow at edges and seams and adequate support to resist positive and negative pressures without displacement or damage. EPA recommends, but does not require, rigid air barriers. Open-cell or closed-cell foam shall have a finished thickness ≥ 5.5 in. or 1.5 in., respectively, to qualify as an air barrier unless the manufacturer indicates otherwise. If flexible air barriers such as house wrap are used, they shall be fully sealed at all seams and edges and supported using fasteners with caps or heads ≥ 1 in. diameter unless otherwise indicated by the manufacturer. Flexible air barriers shall not be made of kraft paper, paper-based products, or other materials that are easily torn. If polyethylene is used, its thickness shall be ≥ 6 mil.

(9) EPA highly recommends, but does not require, an air barrier at the interior vertical surface of floor insulation in Climate Zones 4-8.

(10) Examples of supports necessary for permanent contact include staves for batt insulation or netting for blown-in insulation. Alternatively, supports are not required if batts fill the full depth of the floor cavity, even when compression occurs due to excess insulation, as long as the R-value of the batts has been appropriately assessed based on manufacturer guidance and the only defect preventing the insulation from achieving the required installation grade is the compression caused by the excess insulation.

(11) Alternatively, an air barrier is permitted to be installed at the exterior horizontal surface of the floor insulation if the insulation is installed in contact with this air barrier, the exterior vertical surfaces of the floor cavity are also insulated, and air barriers are included at the exterior vertical surfaces of this insulation.

ENERGY STAR Revision 08 requirements are required for homes permitted starting 07/01/2016.

DOE Zero Energy Ready Home

Exhibit 2: DOE Zero Energy Ready Home Target Home. Certified under ENERGY STAR Qualified Homes Version 3. Insulation levels shall meet or exceed the 2012 IECC (Table R402.1.1) and achieve Grade 1 installation, per RESNET standards. Infiltration (ACH50): Zones 1-2: 3; Zones 3-4: 2.5; Zones 5-7: 2; Zone 8: 1.5. Envelope leakage shall be determined by an approved verifier using a RESNET-approved testing protocol. Steel-frame ceilings, walls, and floors shall meet the insulation requirements of the 2012 IECC – Table 402.2.6.

2009, 2012, and 2015 IECC

Table R402.4.1.1 Air Barrier and Insulation Installation, Floors: Insulation in floors (including above garage and cantilevered floors) is installed to maintain permanent contact with underside of subfloor decking. A continuous air barrier is installed in the building envelope including rim joists and exposed edges of insulation. Breaks or joints in the air barrier are sealed. Air permeable insulation is not used as a sealing material. Junction of foundation and wall sill plates, wall top plate and top of wall, sill plate and rim-band, and rim band and subfloor are sealed. Corners, headers, and rim joists making up the thermal envelope are insulated.* 
Table R402.1.1 (Table R402.1.2 in 2015 IECC) Insulation and Fenestration Requirements – meet or exceed the insulation levels listed in this table.

2009, 2012, and 2015 IRC

Table N1102.4.2  Air Barrier and Insulation Installation, Floors: Insulation in floors (including above garage and cantilevered floors) is installed to maintain permanent contact with underside of subfloor decking. A continuous air barrier is installed in the building envelope including rim joists and exposed edges of insulation. Breaks or joints in the air barrier are sealed. Air permeable insulation is not used as a sealing material. Junction of foundation and wall sill plates, wall top plate and top of wall, sill plate and rim-band, and rim band and subfloor are sealed. Corners, headers, and rim joists making up the thermal envelope are insulated.* 
Table R402.1.1 (Table R402.1.2 in 2015 IECC) Insulation and Fenestration Requirements – meet or exceed the insulation levels listed in this table.

*Due to copyright restrictions, exact code text is not provided. For specific code text, refer to the applicable code.     

More Info.

Contributors to this Guide

The following Building America Teams contributed to the content in this Guide.

Case Studies

None Available

References and Resources*

  1. Author(s): DOE
    Organization(s): DOE
    Publication Date: May, 2015

    Standard requirements for DOE's Zero Energy Ready Home national program certification.

  2. Author(s): EPA
    Organization(s): EPA
    Publication Date: September, 2015

    Document outlining the program requirements for ENERGY STAR Certified Homes, Version 3 (Rev. 08).

  3. Author(s): APA - The Engineered Wood Association
    Organization(s): APA - The Engineered Wood Association
  4. Author(s): EPA
    Organization(s): EPA
    Publication Date: January, 2008

    Document providing an overview of the Thermal Bypass Checklist for the ENERGY STAR Qualified Homes program.

  5. Author(s): EPA
    Organization(s): EPA
    Publication Date: October, 2011

    Guide describing details that serve as a visual reference for each of the line items in the Thermal Enclosure System Rater Checklist.

  6. Author(s): DOE
    Organization(s): DOE
    Publication Date: May, 2012

    Information sheet about types and installation of insulation.

Building Science-to-Sales Translator

Fully Aligned Air Barriers =
Whole-House Draft Barrier

Technical Description: 

A whole-house draft barrier is a continuously connected layer of solid or air-tight materials that block air leaks. This barrier can also function as part of a water barrier, thermal barrier, and vapor barrier, if the location and materials are compatible. For example, rigid foam insulation can provide a combined function. Rigid foam sheets can be used to block air flow when seams are sealed with tape, caulks or adhesives, or liquid applied sealants. An example of an interior air barrier may be the drywall on the home’s walls and ceilings, when the seams are taped and mudded, and caulk, spray foam, or gaskets are used to seal around wiring, plumbing, and other penetrations. Insulation should be in full contact with the air barrier layer.

Alternate Terms

Air Contaminant Barrier
Energy Saving Air Barrier
Advanced Air Barrier Technology
Professionally-Installed Draft Barrier
Moisture Control Air Barrier
Whole-House Draft Barrier
Sales Message
Whole-house draft barriers block air flow that can undermine the thermal protection with a complete high-performance insulation system. What this means to you is less wasted energy along with enhanced comfort, quiet, and durability. Wouldn’t you agree it would be a shame to only get a partial return on your investment in advanced insulation?
Last Updated: 03/14/2016

Mobile Field Kit

The Building America Field Kit allows you to save items to your profile for review or use on-site.