Skip to main content

Defensible Space for Protection Against Wildfires

    Scope
    Scope Images
    Image
    Create defensible space against wildfires by limiting fire fuels in the immediate, intermediate, and extended zones around the home
    Scope

    In high-risk fire hazard areas, such as at the wildland-urban interface (WUI), create defensible space between the house and potential wildfire fuels to protect the building from ignition during a wildfire event.

    • Immediate zone: Establish and maintain a noncombustible zone that includes the house and the area within a 5-foot perimeter around the house by removing vegetation and installing noncombustible ground cover materials such as rock, stone, gravel, or pavers. No tree branches should extend into this space. Follow best practices for selecting fire-resistant materials and constructing the home for fire-resistance.
    • Intermediate zone: In the area between 5 feet and 30 feet from the perimeter of the house, employ noncombustible landscaping, remove excess vegetation, and leave in place or plant only vegetation that is selected and spaced to reduce the risk of wildfire. Employ noncombustible or low-fire-risk ground covers to interrupt the potential path of an oncoming fire. Canopies (branches) of mature trees should be at least 10 feet from the structure and at least 18 feet apart, or more on slopes.
    • Extended zone: In the area between 30 feet and 100 feet from the perimeter of the house, remove excess vegetation and leave in place or plant only vegetation that is selected and spaced to reduce the risk of wildfire. Use noncombustible or low-fire-risk ground covers to interrupt the potential path of an oncoming fire. At 30 to 60 feet from the home, canopies of mature trees should be at least 12 feet apart from each other. At 60 or more feet from the home, canopies of mature trees should be at least 6 feet apart from each other.
    • Provide guidance to the homeowner for ongoing reducing, pruning, and thinning of vegetation and removal of debris in these zones to minimize potential wildfire fuel. 

    See the Compliance Tab for related codes and standards requirements, and criteria to meet national programs such as DOE’s Zero Energy Ready Home programENERGY STAR Single-Family New Homes, and Indoor airPLUS.

    Description
    Description

    The U.S. Fire Administration (USFA) estimates more than 46 million residences in 70,000 communities throughout the United States are at risk for WUI fires (USFA 2021). Although protecting a home during a wildfire event may seem hopeless, research has shown that builders and residents who take the proper precautions can significantly reduce the risk of their homes igniting (Figure 1).

    This home has defensible space around it, with a vegetation-free zone that helped the house survive a surrounding wildfire.
    Figure 1. This home has defensible space around it, with a vegetation-free zone that helped the house survive a surrounding wildfire (Source: Courtesy of FireWise USA).

     

    A basic understanding of the physical factors affecting wildfire spread is important for determining how to best prepare a property to increase its wildfire resistance. There are three main factors that contribute to how a wildfire spreads: weather, topography, and fuels. Prolonged periods of hot and dry weather can dry out vegetation, making it easier to ignite, and windy conditions can increase the supply of oxygen to a fire and preheat fuel sources in front of the fire. Topography also affects the spread of wildfire. For example, steep slopes carry fire up hill at an increased rate and canyons create wind channels that also increase burn rate. The last factor affecting wildfire spread is fuel. Fuel for a wildfire can take many forms, from living or dead vegetation to homes or outbuildings. Of the three factors that affect wildfire behavior, fuels are the easiest for builders and homeowners to manage in terms of reducing wildfire spread and the risk of home ignition.   

    The area surrounding a house where fire fuel, such as trees and other vegetation, has been managed to mitigate the spread of fire is referred to as defensible space. Defensible space is one of the most important factors in determining a house’s ability to survive a wildfire. Management of fuels surrounding a house encompasses careful landscape planning, such as appropriate spacing of trees, careful selection of vegetation, and installation of fire fuel breaks including driveways, walkways, and noncombustible ground covers. Use of defensible space helps to mitigate the spread of fire from one area of a property to another and to structures on the property. The term “defensible space” was coined in the 1980s to describe vegetation management practices aimed at reducing the wildfire threat to homes, to provide greater opportunity for firefighters to be able to save the home. However, in many cases, firefighting resources are not available to defend every home. Another term, “survival space” is used by some organizations including FireSafe, a non-profit network of councils that provide wildfire safety education. Survivable space refers to modification of the landscape to reduce the amount of wildfire fuel (vegetation) and pathways of fuel to the house and modification to the house design and materials to make a home less likely to be ignited by a wildfire, even without direct firefighter intervention (FireSafe Montana 2009).

    Some definitions of defensible space include a safe area for firefighters to defend the building, which could include turnaround space for emergency vehicles and a two-way access road to the property. This guide will focus on the use of defensible space to reduce the fire threat to the building so that it can have a better chance of surviving without suppression activities by firefighters. During a wildfire conflagration, firefighters may not be available or able to protect the home, based on time, distance, conditions, and other firefighting activity.

    FireWise produces a poster for homeowners listing some of the steps they can take to make a home more defensible and survivable (Figure 2). Builders can take note of some features to include at initial construction or renovation: a wide driveway and preferably pull through or turnaround access for fire fighting vehicles from a lane wide enough for two-way traffic, outbuildings constructed 30 feet from the home or considered part of the home for protection, a screened chimney, easily accessible hose bibs installed on the front and rear of the home, large trees and shrubs not planted near the structure, and noncombustible landscaping installed within the first 30 feet of the structure. Other features not shown on this poster include use of noncombustible or ignition-resistant Class A roofing, siding, and door; double-pane windows with an exterior pane of tempered glass; boxed-in soffits covered with a noncombustible or ignition-resistant material, areas below decks screened or enclosed with ignition-resistant material; and 1/8-inch mesh covering all vent openings.

    How to make your home FireWise
    Figure 2. How to make your home FireWise (Source: FireWise USA).

     

    To create defensible space on residential properties, the National Fire Protection Association (NFPA 2020) recommends property maintenance, with varying degrees of vegetation (i.e., fire fuel) allowed based on distance from the structure. The NFPA defines these areas as the immediate zone (0-5 feet), the intermediate zone (5-30 feet), and the extended zone (30-100 feet) as shown in Figure 3. The Insurance Institute for Building and Home Safety refers to these zones as the Near-Home Noncombustible Zone; the Lean, Clean, and Green Zone; and the Reduced Fuel Zone (IBHS 2019). Local jurisdictions commonly set the requirements for defensible space in local fire, land use, or subdivision codes. The size requirements for defensible space vary by jurisdiction with increased size requirements for areas at higher risk for wildfires. For example, San Diego County requires the intermediate zone to be extended to a 50-foot radius rather than a 30-foot radius of the home. The following guidance on the three zones represent best practices for creating and maintaining defensible space and is taken from several sources (for example, NFPA 2021, IBHS 2019, University of Nevada Cooperative Extension 2018, FireSafe Montana 2009). Consult your local jurisdiction having authority for requirements in your area.

    Create defensible space against wildfires by limiting fire fuels in the immediate, intermediate, and extended zones around the home.
    Figure 3. Create defensible space against wildfires by limiting fire fuels in the immediate, intermediate, and extended zones around the home (Source: Adapted from NFPA 2020).

     

    Immediate Zone –0 to 5 feet, the “Noncombustible Zone”

    The immediate zone includes the home and the area 0 to 5 feet from the furthest attached exterior point of the home. This zone should not include any combustible materials or vegetation. A majority of wildland house fires are started by flying embers. Embers from a distant fire can become airborne and start fires outside a house where flammable vegetation exists or inside a house by floating in through open windows or attic or crawlspace vents.  Therefore, special attention should be paid to managing potential fuels in the immediate zone around the house and covering all vents with metal screening, in addition to building the home itself from fire-resistant materials. Take the following steps to make the exterior of the home and area within 5 feet around it a noncombustible zone. Links are provided to other guides in the Solution Center that provide more detail on these measures.

    • Construct the roof, siding, decks, porches, carports, and railings from fire-resistant or noncombustible materials.
    • Install 1/8-inch metal mesh screening on all vents to prevent ember intrusion. Where screening is already installed, inspect to ensure the screens are not damaged. Replace damaged screening.
    • Design or retrofit eaves to be enclosed with a horizontal soffit cover to reduce the chance of trapping embers among rafter tails in open soffits. Attic vent openings can be installed in the vertical fascia rather than in the underside of the fascia.
    • Consider constructing the home with an unvented attic and unvented soffits.
    • If constructing the walls with a ventilation gap behind the cladding, install screening with holes that are 1/8 inch or smaller at the top and bottom of the walls to keep embers and bugs out of the air gap.
    • If curved tile roofs are installed, close off the ends with bird-stopping materials to prevent birds from building nests which can be a fire fuel source.
    • Screen or box-in areas below decks to prevent debris accumulation.
    • Remove vegetation and flammable material from wall exteriors and from underneath decks, porches, or cantilevers.
    • Advise the homeowner to keep roofs and gutters free of debris and leaves to prevent ignition from embers and to replace or repair loose or missing shingles on roofs, loose or damaged window screens, and broken windows to reduce the risk of fire or ember entry.
    • Establish a 5-foot perimeter around the house that has a very low potential for ignition from flying embers. Keep the area free of woodpiles, wood mulches, dead plants, dried leaves and needles, trees, and shrubs (sagebrush and juniper are especially flammable).
    • Install noncombustible ground cover materials such as rock, stone, gravel, or pavers.

    Intermediate Zone – 5 to 30 feet, the “Clean and Green Zone”

    The intermediate zone is the zone 5 to 30 feet from the furthest attached exterior point of the home. Employ fire-resistant plants and noncombustible landscaping features, create breaks in vegetation, and remove excess vegetation to help decrease fire spread.

    • During house construction, clear the site and keep or plant only those trees that have been intentionally selected or spaced to minimize fire hazards, as shown in Figure 4. Limit trees to individual trees or small clusters of two or three trees. Plan for a minimum spacing of at least 18 feet between the canopies of mature trees or tree clusters. Allow more spacing if trees are on sloped ground. Choose deciduous over coniferous trees.
    • Create fuel breaks with driveways, walkways, patios, and decks.
    • Advise the homeowner to:
      • Maintain lawns and native grasses to a maximum height of four inches and irrigate if needed.
      • Remove “ladder fuels,” i.e., vegetation under trees and low branches, so surface fires cannot reach the upper branches. Prune trees by removing branches from the ground up 6 to 10 feet above the ground (depending on the height of the tree). Remove or prune shrubs so the shrubs do no exceed one-third of the overall tree height.
      • Ensure tree branches are no closer than 10 feet to the edge of the house and at least 15 feet from chimneys.
      • Clear away vegetation from under large stationary propane or fuel tanks.
      • Remove dead or dying vegetation, leaves, and pine needles.
      • Have garden hose on hand that can reach to all sides of the structure.
    Recommended tree spacing for wildfire resistance within the immediate, intermediate, and extended defensible space zones (note, these zones should extend an equal distance from the home in all directions).
    Figure 4. Recommended tree spacing for wildfire resistance within the immediate, intermediate, and extended defensible space zones (note, these zones should extend an equal distance from the home in all directions) (Source: National Fire Protection Association 2020).

     

    Extended Zone – 30 to 100 feet, the “Reduced Fuel Zone”

    The extended zone is the area 30 to 100 feet from the furthest attached exterior point of the home (or to the property line).

    • Remove dead vegetation and trees.
    • Dispose of debris and litter accumulation.
    • Remove small conifers growing between mature trees.
    • Remove vegetation adjacent to outbuildings.
    • At 30 to 60 feet from the perimeter of the house, space trees and tree clusters to have at least 12 feet between canopy tops (branches) from one tree to another.
    •  At 60 to 100 feet from the perimeter of the house, mature trees and tree clusters should have at least 6 feet between the canopy tops.
    • Trim branches back 10 feet from each side of access roads.
    • Homes located at the end of long driveways or dead-end roads should have turn-around areas suitable for large fire equipment. Turn-arounds can be a cul-de-sac with at least a 45-foot radius or a location suitable for a three-point turn (University of Nevada Cooperative Extension 2018).
    • House numbers should be readily visible from the street. The address sign should be made of reflective, noncombustible material with characters at least 4 inches high (University of Nevada Cooperative Extension 2018).

    The distances listed for crown spacing are suggested based on NFPA 1144. However, the crown spacing needed to reduce or prevent the potential for crown fires could be significantly greater due to slope, the species of trees involved, and other site-specific conditions. Follow guidelines in Figure 5 and Figure 6 for vertical and horizontal spacing recommendations. For forested areas beyond the extended zone that surround homes or communities, forest fire travel can be slowed or stopped by employing green strips (Figure 7) and shaded fuel breaks (Figure 8) (University of Nevada Cooperative Extension 2018).

    Many homes have defensible space areas that extend into neighboring properties. It is recommended that homeowners work with their neighbors in creating defensible space to collectively reduce wildfire risk within the community. Defensible space principles can also be applied to a community surrounded by natural vegetation (University of Nevada Cooperative Extension 2018; Figure 9). Some areas have established community wildfire protection plans. For example, the National Fire Protection Association (NFPA)’s FireWise USA® program provides a collaborative framework to assist homeowners in a geographic area in organizing and taking action to increase the survivability of their homes and communities. Use the interactive map on the FireWise USA® website to see if the home is located within a FireWise USA® community.

    The minimum horizontal clearance needed between trees and shrubs to increase wildfire resistance increases with slope.
    Figure 5. The minimum horizontal clearance needed between trees and shrubs to increase wildfire resistance increases with slope (Source: Los Gatos 2021).

     

    Minimum vertical clearances needed between trees and the ground or shrubs to reduce the spread of wildfires.
    Figure 6. Minimum vertical clearances needed between trees and the ground or shrubs to reduce the spread of wildfires (Source: Los Gatos 2021).

     

    A green strip is a type of fuel break planted with less flammable vegetation; e.g., crested wheatgrass.
    Figure 7. A green strip is a type of fuel break planted with less flammable vegetation; e.g., crested wheatgrass (Source: University of Nevada Cooperative Extension 2018).

     

    A shaded fuel break is created on forested lands when trees are thinned, tree canopies are raised by removing lower branches, and the understory vegetation is managed to reduce the fire threat.
    Figure 8. A shaded fuel break is created on forested lands when trees are thinned, tree canopies are raised by removing lower branches, and the understory vegetation is managed to reduce the fire threat (Source: University of Nevada Cooperative Extension 2018).

     

    Fire resistance plans for a community include creating defensible space for each home and for the whole community, constructing with fire-resistant materials, and providing turn-around space for emergency response vehicles.
    Figure 9. Fire resistance plans for a community include creating defensible space for each home and for the whole community, constructing with fire-resistant materials, and providing turn-around space for emergency response vehicles (Source: University of Nevada Cooperative Extension 2018).

     

    Success
    Ensuring Success

    To ensure successful creation and maintenance of defensible space, encourage the homeowner to conduct an annual fire hazard risk assessment and property clean-up a few months before the wildfire season starts. Most local fire departments offer voluntary fire and defensible space inspections. Many states have adopted provisions of the 2018 National Fire Protection Association Standard for Reducing Structure Ignition Hazards from Wildland Fire (NFPA 1144) and 19 states have adopted provisions of the International Wildland-Urban Interface Code (IWUIC). Since 2005 the State of California has required homeowners in designated wildfire-prone areas to create 100 feet of defensible space around their homes (IBHS 2019). In addition to state codes, many municipalities, especially those located in the WUI, have adopted municipal code ordinances regarding fire safety, in some cases more restrictive than those adopted by the state. Verify fire-related code requirements with the municipality having jurisdiction over the building site. 

    Climate
    Climate

    The U.S. Forest Service offers a website with interactive maps and charts to help communities explore wildfire risk. Houses built in wildland-urban interfaces in hot and dry climates are especially susceptible to wildfire events. Proper creation of defensible space is even more important in these areas to minimize the risk of home ignition and slow the spread of wildfire within the community.

    Specific wildfire risks vary by region and are dependent on topography, native vegetation, building styles, and the quality of state and local building codes. The Insurance institute for Business and Home Safety® (IBHS) provides regional guides that offer region-specific guidance, best practices, and voluntary standards for creating defensible space (IBHS 2021).

    Contact the local forestry agency or fire department to learn more about the specific wildfire risks where you are building.

    Training
    Right and Wrong Images
    Image
    Right - Leaf guards allow rainwater into the gutter but keep combustible debris out, increasing the home's resistance to wildfires.
    Right - Leaf guards allow rainwater into the gutter but keep combustible debris out, increasing the home's resistance to wildfires.
    Image
    Wrong - Debris in these open gutters can ignite from wind-borne embers and lead to ignition of the roof or fascia board; use leaf screens to keep debris out of gutters in wildfire-prone areas.
    Wrong - Debris in these open gutters can ignite from wind-borne embers and lead to ignition of the roof or fascia board; use leaf screens to keep debris out of gutters in wildfire-prone areas.
    Image
    Wrong – Combustible debris under this deck ignited and led to the destruction of the deck.
    Wrong – Combustible debris under this deck ignited and led to the destruction of the deck.
    Image
    Wrong – Airborne embers can float into holes in damaged vent screens and ignite flammable items in the house or accumulated debris in the vent.
    Wrong – Airborne embers can float into holes in damaged vent screens and ignite flammable items in the house or accumulated debris in the vent.
    Image
    Right – A non-combustible 1/8-inch mesh screen is installed on vent openings to reduce the risk of fire from intrusion of wind-borne embers.
    Right – A non-combustible 1/8-inch mesh screen is installed on vent openings to reduce the risk of fire from intrusion of wind-borne embers.
    Image
    Wrong – Tree branches close to the house are prone to spreading crown fires to the house; the tree should be trimmed so that branches are at least 10 feet back from the red dashed line indicating the deck railing of the house.
    Wrong – Tree branches close to the house are prone to spreading crown fires to the house; the tree should be trimmed so that branches are at least 10 feet back from the red dashed line indicating the deck railing of the house.
    Image
    Right – Trimming tree branches a minimum of 10 feet from the house or any attached structures reduces the risk of home ignition.
    Right – Trimming tree branches a minimum of 10 feet from the house or any attached structures reduces the risk of home ignition.
    Presentations
    Author(s)
    National Fire Protection Association
    Organization(s)
    NFPA
    Publication Date
    Description
    Presentation of an online learning module that teaches residents basic information about how wildfires start, how they spread, and how they are most likely to burn houses, with some homeowner guidance for reducing wildfire risk.
    Videos
    Publication Date
    Author(s)
    UNRExtension
    Organization(s)
    UNRExtension
    Description
    Video interview from the University of Nevado - Reno with a Nevada fire protections officer explaining how to properly inspect a home's defensible space.
    Publication Date
    Author(s)
    USDA Forest Service National Interagency Fire Center,
    National Fire Prevention Education Teams
    Organization(s)
    NFPA,
    USDA Forest Service
    Description
    Video from USDA Forest Service explaining the benefits that community education can have on lowering wildfire risks.
    Compliance

    Compliance

    The Compliance tab contains both program and code information. Code language is excerpted and summarized below. For exact code language, refer to the applicable code, which may require purchase from the publisher. While we continually update our database, links may have changed since posting. Please contact our webmaster if you find broken links.

     

    Consult the local or state fire agency about codes, requirements, and standards related to defensible space.

     

    2012, 2015, and 2018 International Wildland-Urban Interface Code (IWUIC)

    Section 603.2 Fuel Modification – Buildings or structures, constructed in compliance with the conforming defensible space category of Table 503.1, shall comply with the fuel modification distances contained in Table 603.2. For all other purposes the fuel modification distance shall be not less than 30 feet (9144 mm) or to the lot line, whichever is less. Distances specified in Table 603.2 shall be measured on a horizontal plane from the perimeter or project of the building or structure as shown in Figure 603.2. Distances specified in Table 603.2 are allowed to be increased by the code official because of a site-specific analysis based on local conditions and the fire protection plan.

    Section 603.2.2 Trees – Trees are allowed within the defensible space, provided that the horizontal distance between crowns of adjacent trees and crowns of trees and structures, overhead electrical facilities or unmodified fuel is not less than 10 feet (3048 mm).

    Section 603.2.3 Ground Cover – Deadwood and litter shall be regularly removed from trees. Where ornamental vegetative fuels or cultivated ground cover, such as green grass, ivy, succulents or similar plants are used as ground cover, they are allowed to be within the designated defensible space, provided that they do not form a means of transmitting fire from the native growth to any structure.

    Section 604.2 Modified area – Nonfire-resistive vegetation or growth shall be kept clear of buildings or structures, in accordance with Section 603, in such a manner as to provide a clear area for fire suppression operations.

    Section 604.4 Trees – Tree crowns extending to within 10 feet (3048 mm) of any structure shall be pruned to maintain a minimum horizontal clearance of 10 feet (3048 mm). Tree crowns within the defensible space shall be pruned to remove limbs located less than 6 feet (1829 mm) above the ground surface adjacent to trees.

    Section 604.4.1 Chimney clearance – Portions of tree crowns that extend to within 10 feet (3048 mm) of the outlet of a chimney shall be pruned to maintain a minimum horizontal clearance of 10 feet (3048 mm).

    Section 604.4.2 Deadwood removed – Deadwood and litter shall be regularly removed from trees.

     

    2018 National Fire Protection Association Standard for Reducing Structure Ignition Hazards from Wildland Fire (NFPA 1144)

    Section 5.1.3.4 Vegetation shall be modified to mitigate hazardous conditions within 30 ft (9m) of the foundations prior to the start of construction.

    Section 5.1.3.5 All slash from vegetation modification and construction debris shall be treated or removed prior to or immediately upon completion of construction.

    Section 5.3.2 Roof gutters, downspouts, and connectors shall be noncombustible, and roof gutters shall be covered with an approved noncombustible means to minimize the accumulation of debris.

    Section 5.3.3 Vents or vent assemblies shall resist the intrusion of flames and embers according to either of the following:

    (1) Vents shall be screened with corrosion-resistant noncombustible wire mesh with the mesh opening not to exceed nominal 1/8 in (3.1 mm) in size.

    (2) Vents and assemblies shall demonstrate the ability to resist the intrusion of flame or embers through the opening when tested in accordance with ASTM E2886, Test Method for Evaluating the Ability of Exterior Vents to Resist the Entry of Embers and Direct Flame Impingement, and comply with all of the following:

    (a) There shall be no flaming ignition of the cotton material during the Ember Intrusion Test.

    (b) There shall be no flaming ignition during the Integrity Test portion of the Flame Intrusion Test.

    (c) The maximum temperature of the unexposed side of the vent shall not exceed 662°F (350°C).

    Section 5.3.4 Eaves shall be enclosed with exterior fire-retardant-treated wood, ignition-resistant materials, noncombustible materials, or materials exhibiting resistance to wildfire penetration when tested to ASTM E2957-15, Standard Test Method for Resistance to Wildfire Penetration of Eaves, Soffits and Other Projections.

    Section 6.21 Ground fuels, including native vegetation and plants used for landscaping within the defined landscaping zones, shall be treated or removed.  

    Section 6.2.2 Live vegetation within the fuel modification area shall have dead material removed and shall be thinned and pruned in conformance with the wildland fire mitigation plan, as approved by the AHJ.

    Section 6.2.3 Dead and downed fuels within 30 ft (9 m) of all buildings shall be removed or treated to maintain the fuel modification area in conformance with the wildland fire mitigation plan, as approved by the AHJ.

    Section 6.2.4 Vegetation under trees within the fuel modification area shall be maintained at a height that will preclude ground fire from spreading in the tree crown.

    Section 6.2.5 Tree crowns within the structure ignition zone shall be spaced to prevent structure ignition from radiant heat. Section 6.2.6 The fuel modification plan shall include a maintenance element identifying and defining the responsibility for continued and periodic maintenance.

    Retrofit
    Existing Homes

    The recommendations provided in this guide for new homes also apply to existing homes.

    More

    More Info.

    Access to some references may require purchase from the publisher. While we continually update our database, links may have changed since posting. Please contact our webmaster if you find broken links.

    References and Resources*
    Author(s)
    National Fire Protection Association
    Organization(s)
    NFPA
    Publication Date
    Description
    Website describing methods for homeowners to prepare their homes to withstand ember attacks and minimize the likelihood of flames or surface fire touching the home or any attachments.
    Author(s)
    Insurance Institute for Business & Home Safety
    Organization(s)
    IBHS
    Publication Date
    Description
    Webpage that provides regional guides to help home and business owners prioritize necessary retrofit projects for wildfire resistance.
    Author(s)
    California Department of Forestry and Fire Protection
    Organization(s)
    Cal Fire
    Publication Date
    Description
    A webpage outlining CAL FIRE’s recommendations for creating defensible space.
    Author(s)
    Town of Los Gatos California
    Organization(s)
    Town of Los Gatos California
    Publication Date
    Description
    A webpage outlining recommendations for creating defensible space.
    Author(s)
    U.S. Fire Administration
    Organization(s)
    U.S. Fire Administration
    Publication Date
    Description
    A webpage that provides wildfire preparedness and safety pictographs.
    Author(s)
    Bueche David,
    Foley Tim
    Organization(s)
    Colorado State Forest Service,
    CSFS
    Publication Date
    Description
    Wildfire construction guidelines from the Colorado State Forest Service focusing on site design and building materials to mitigate damage to homes in wildfire-prone areas.
    Author(s)
    DisasterSafety.org
    Organization(s)
    IBHS
    Publication Date
    Description
    A webpage providing guidance on increasing the wildfire resistance of a home.
    Author(s)
    U.S. Department of Agriculture
    Organization(s)
    USDA,
    USDA Forest Service
    Publication Date
    Description
    A website created by the U.S. Forest Service, containing interactive maps, charts and resources to help communities explore their risk to wildfires.
    Author(s)
    FireSafe Montana
    Organization(s)
    FireSafe Montana
    Publication Date
    Description
    Guide for homeowners describing actions they can take to modify their home and the surrounding site to create a survivable space to reduce the amount of damage a home would likely experience during a wildfire.
    Author(s)
    U.S. Forest Service
    Organization(s)
    USDA
    Publication Date
    Description
    Article describing the growth of the wildland urban interface in the United States from 1990 to 2010, expanding from 30.8 to 43.4 million homes (a 41% increase), and growing from 581,000 to 770,000 kM2 (33% growth), an increase of 189,000 km2, an area that is larger than Washington State.
    *For non-dated media, such as websites, the date listed is the date accessed.
    Contributors to this Guide

    The following authors and organizations contributed to the content in this Guide.

    Pacific Northwest National Laboratory

    Last Updated

    Did you find this information helpful?

    If you have questions and/or would like a reply to this feedback, please include your e-mail address in the message.
    This question is for testing whether or not you are a human visitor and to prevent automated spam submissions.