Roof Vents

Scope Images
Right – Baffles maintain air flow above attic insulation
Right – Baffles maintain air flow above attic insulation
Scope

If constructing a vented attic in a high-wind or wildfire-prone region, construct the soffit assembly and upper roof/attic vents to resist wind pressures and wind-driven rain and snow entry and to provide more robust wildfire resiliency.

  • Select and install upper roof attic vents that resist the entry of wind-blown rain, snow, and embers. IBHS Fortified Home recommends that vent models be certified as resistant to wind and water intrusion in accordance with Florida Building Code TAS 100 (A).
  • In hurricane zones, IBHS Fortified Home recommends not installing gable end vents in new homes. Use certified, properly installed ridge or off-ridge vents rather than gable vents. For existing homes that have gable vents, either permanently block the gable vents or provide removable or operable exterior coverings or interior shutters that can be installed when a hurricane threatens and removed when the threat has passed. Permanent mounting anchors should be installed for shutters.  
  • Vinyl and aluminum soffits must be installed in accordance with the manufacturer’s installation instructions and should not exceed 12 inches between support members.
  • Gable end soffits should not be vented.
  • Consider designing and constructing the soffit assembly to provide “two-stage” air pressure control using a continuous narrow soffit strip vent coupled with an expansion chamber followed by a narrow structural baffle.
  • For new construction, consider designing the home with an unvented attic. For existing homes, consider converting a vented attic to an unvented attic.

See the Compliance Tab for related codes and standards requirements, and criteria to meet national programs such as DOE’s Zero Energy Ready Home program, ENERGY STAR Certified Homes, and Indoor airPLUS.

Description

In high-wind zones, roof assemblies need to be able to resist the wind pressures that can act on them during high-wind events such as hurricanes. In wildfire events, one of the most common means of homes catching fire is the entry of airborne embers into vented roof assemblies through roof vents.

The most common type of residential roof assembly is a vented attic. The most common damage occurring to residential buildings during high-wind events is rainwater entry and one of the most common pathways for rainwater entry is through roof vents.

For the best resistance to wind-borne rain and embers, in new construction, consider designing the home with an unvented attic. For existing homes, consider converting a vented attic to an unvented attic.

When soffit vents are coupled with upper roof vents, the intent is to provide “balanced attic ventilation” where the vent area of the soffit vents matches the vent area of the upper vents. The applicable building codes provide for a total attic vent area (1:300 vent ratio) for balanced ventilation. 

Upper roof/attic vents are generally of three types: ridge vents (Figure 1), off-ridge button or mushroom vents (Figure 2), and gable-end vents (Figure 3). Select and install upper roof attic vents that resist the entry of wind-blown rain, snow, and embers. The Insurance Institute for Business and Home Safety (IBHS) Fortified Home program recommends that vent models be certified as resistant to wind and water intrusion in accordance with Florida Building Code TAS 100 (A). Certain jurisdictions have specific performance requirements for roof vent performance. See for example this roof vent checklist from Miami-Dade County.

In general, gable end vents should not be used in conjunction with ridge or off-ridge vents because the gable-end vents are likely to “short-circuit” attic air flow. Lower soffit vents are intended to “supply” air to the attic space and the upper roof/attic vents are intended to “exhaust” air from the attic space. Gable end vents, when installed in an attic that also has ridge vents, can render soffit venting ineffective.

In hurricane and high-wind locations, the IBHS Fortified Home program recommends not installing gable end vents in new homes. Use certified, properly installed ridge or off-ridge vents rather than gable vents. For existing homes that have gable vents, either permanently block the gable vents or provide removable or operable exterior or interior coverings or shutters that can be installed when a hurricane threatens and removed when the threat has passed. Permanent mounting anchors should be installed for these coverings. 

Vinyl and aluminum soffit vents must be installed in accordance with the manufacturer’s installation instructions and support framing should be spaced no further than 12 inches apart. Gable end soffits should not be vented.

Upper roof/attic vents are intended to provide exhaust airflow and therefore should experience negative pressure or “suction” during wind events. Upper roof/attic vents should be selected with built-in baffles or “lips” that provide turbulence and suction regardless of wind direction. Ridge vents are more effective than button/off-ridge vents in this regard.

To provide more robust wildfire resiliency, mesh screening should be installed at soffit vent openings. The recommended mesh size is 1/8 inch (3 mm) or less. Ridge vents for wildfire resiliency should be selected that are compliant with Miami-Dade wind-driven rain requirements. Ridge vents that are effective at wind-driven rain control are also effective in controlling the entry of airborne embers or cinders.

One approach may be to forgo upper attic and ridge vents completely. Experience has shown that it is easier to prevent or control rainwater entry in soffit assemblies than in upper roof vents. As such, providing “robust” soffit venting and not installing upper roof vents reduces the risk of rainwater entry during high-wind events. This approach also reduces the risk of roof sheathing “blow off” and loss of the roof structure. Upper roof vents can get “sucked” off roof assemblies on the leeward “negative air pressure” side of the building in high winds. When the wind changes direction, the resulting large openings can allow pressurization of the attic space and loss of the structure. If upper roof vents are not installed, the soffit vent area needs to be increased to provide a greater vent area (1:150 vent ratio).

If the attic will be vented with soffit vents (with or without upper attic vents), consider designing and constructing the soffit assembly to provide “two-stage” air pressure control using a continuous “narrow” soffit strip vent coupled with an “expansion chamber” followed by a narrow “structural baffle,” as described below.

The best practice in high wind or high wildfire risk areas may be to design roofs with an unvented attic assembly.

Right – A continuous ridge vent provides full ventilation to a vented attic.
Figure 1. A continuous ridge vent extends the length of the ridge of a gable roof and is concealed by ridge tiles or shingles. (Source: Building Science Corporation).
Right – Button vents work in conjunction with soffit vents to provide ventilation to a vented attic.
Figure 2. Button vents are an alternative to ridge vents for providing ventilation for a vented attic. (Source: Building Science Corporation).
Wrong – Gable end vents can circumvent soffit-to-ridge airflow and allow in wind-driven rain and wildfire embers.

Figure 3. Gable-end vents can circumvent soffit-to-ridge airflow and allow in wind-driven rain and wildfire embers. (Source: Building Science Corporation).

Air Pressures and Roof Venting

Testing conducted by the Insurance Institute for Business and Home Safety (IBHS) has shown that soffit eave vents perform better in controlling airborne embers and cinders than “open-eave” vents. This is believed to be due to the air pressure control provided by a “two-stage” approach. (See the report Vulnerability of Vents to Wind-Blown Embers by IBHS 2017).

Significant air pressure differences act across buildings due to the action of wind. In general, building assemblies experience positive wind pressures on the windward side and negative wind pressures on the leeward side of the roof. 

Attic spaces that are ventilated typically have soffit vents, which consist of a continuous ventilation opening (“strip vent”) and an insulation baffle that maintains an air gap typically 1 to 2 inches deep between the underside of the roof sheathing and the top surface of the insulation layer (Figure 4 and Figure 5). The insulation baffles extend several inches above the top surface of the ceiling insulation. The function of the baffles is to maintain a vent space and to prevent wind from ”washing” through fibrous insulation and from dislodging insulation. The baffle should be sealed to the top plate or wall sheathing to limit “wind washing.” Insulation baffles are often thin sheets of polystyrene foam or cardboard; they are unable to resist significant wind pressures.

Right – Sheathing extends to rafters adding strength to soffit, baffles keep attic insulation from vent to maintain air flow.
Figure 4. A typical vented soffit assembly includes a strip vent and a baffle to maintain an air gap between the insulation and the roof deck. (Source: Building Science Corporation).

Soffit vent openings are prone to rainwater entry and snow entry as a result of wind (Figure 6). In most soffit assemblies, there is little or no resistance to air flow or air pressure differences. Soffit vents, ridge vents, or round vents placed near the roof ridge, and baffles or ventilation chutes are installed to work together to provide air flow up along the underside of the roof deck. Attic ventilation air (“air flow”) is intended to be supplied by soffit vent openings to provide control of moisture in the attic space via the process of dilution air change. However, too much “air flow” leads to rainwater entry during high wind events. In cold climates, too much air flow leads to snow entry (“blown snow’) into attic spaces. Additionally, during wildfire events, burning embers and cinders can be carried into attic spaces.

In high-wind events, if soffit assemblies collapse, excessive wind can enter the attic space on the windward side, pressurizing the attic space. When this positive pressure in the attic is coupled with the negative pressure on the exterior surfaces of the leeward side of the building, the air pressure difference across the roof sheathing and roof cladding elements such as the shingles, tiles, and metal roofing significantly increases. This significant air pressure increase can lead to loss of the roof structure.

Soffit rainwater entry, snow entry, and airborne ember entry can be controlled by constructing the soffit assembly in such a way that it provides “two-stage” air pressure control (Figure 7). This approach also can prevent soffit assembly collapse if the pressure control layers are also “structural.” The approach involves a continuous “narrow” structural soffit strip vent coupled with an “expansion chamber” followed by a narrow “structural baffle” (Figure 3). Any rain and snow that enter are deposited in the soffit “chamber” and do not enter the attic space. High wind pressure events are resisted by the use of “robust” soffit materials (plywood, oriented stand board (OSB), fiber cement, cellular PVC) and structural wood blocking, which provide the “baffle” as shown in Figure 7. Alternatively, exterior structural sheathing in wood frame construction can be extended up past the top plate to act as the “structural baffle” or wind dam as shown in Figures 8 and 9. This structural baffle also provides needed additional structural support for raised heel trusses in high wind zones. A plastic or foam ventilation chute can be attached to this wood baffle. Metal soffit vent grilles or vinyl vent covers installed per manufacturers instructions that are mechanically fastened in place every 12 inches or less should be used rather than perforated vinyl soffit coverings set in J channels as the vinyl is likely to collapse in in high winds, enabling wind to rush in and pressurize the roof which can lead to roof failure.

Wrong - Wind-driven rain and wildfire embers can enter an attic through the soffit vents.
Figure 6. In hurricane- or wildfire-prone regions, wind-driven rain and wildfire embers can enter an attic through the soffit vents. (Source: Building Science Corporation).
Right – “Two-stage” soffit assembly minimizes rainwater entry into attic.

Figure 7. Adding blocking to a vented soffit assembly increases pressure as air enters the narrowed soffit vent then decreases pressure in the wider soffit chamber, then increases pressure by narrowing the attic entry; this design encourages rain to fall out in the chamber. (Source: Building Science Corporation).

 

These raised heel roof trusses provide 16 inches of space over the outer walls for full insulation coverage at the attic perimeter.

Figure 8. The exterior wall sheathing extends to the top of the raised heel trusses providing structural support for raised heel trusses in high-wind zones. (Source: Thrive Home Builders).

 

After all holes through the ceiling are air sealed and the baffles have been installed, the insulation can be installed in full contact with the ceiling drywall, which is the air barrier
Figure 9. The exterior wall sheathing, which extends to the top of the raised heel trusses, provides a structural wind dam that can resist high winds and keep wind-driven rain from blowing through the insulation. (Source: PNNL).

 

 

 

Ensuring Success

In high-wind zones, soffits should be fastened to support structures every 12 inches to resist the air pressures acting on the soffit to prevent soffit collapse and pressurization of the attic space and potential loss of the structure.

Per IBHS, vent models should be certified as resistant to wind and water intrusion in accordance with Florida Building Code TAS 100 (A). These vents will also prevent entry by wind-borne embers.

Vented attics should incorporate a soffit design that uses “two-stage” joint pressure control.

Consider designing the home with an unvented attic.

Climate

If constructing a vented attic in a high-wind or wildfire-prone region, construct the soffit assembly and upper roof/attic vents to resist wind pressures and wind-driven rain and snow entry and to provide more robust wildfire resiliency.

  • Select and install upper roof attic vents that resist the entry of wind-blown rain, snow, and embers. IBHS Fortified Home recommends that vent models be certified as resistant to wind and water intrusion in accordance with Florida Building Code TAS 100 (A).
  • In hurricane zones, IBHS Fortified Home recommends not installing gable end vents in new homes. Use certified, properly installed ridge or off-ridge vents rather than gable vents. For existing homes that have gable vents, either permanently block the gable vents or provide removable or operable exterior coverings or interior shutters that can be installed when a hurricane threatens and removed when the threat has passed. Permanent mounting anchors should be installed for shutters.  
  • Vinyl and aluminum soffits should be installed in accordance with the manufacturer’s installation instructions and should not exceed 12 inches between support members.
  • Gable end soffits should not be vented.
  • The eave should be covered with a soffit. Open eaves can trap hot air, gases, and embers (Figure 1). If the soffit is applied directly to the rafter eave, it forms a sloping soffit, which creates a pocket that can trap fire (Figure 2). It is preferable to construct a flat soffit (Figure 3) that allows the structure to more readily deflect fire outward. Unvented soffits (and unvented attics) are more resistant to fires than vented attics. If the eaves must be vented, place the vents further from the wall and closer to the fascia or in the fascia itself and metal mesh screening should be installed in the vent openings with a mesh size of 1/8 inch (3mm) or less (Source: CSFS 2012).

Wrong - An open eave with no soffit covering can trap rising hot air and embers from a wildfire
Figure 1. Wrong - An open eave with no soffit covering can trap rising hot air and embers from a wildfire (Source: CSFS 2012).
Wrong - If the soffit is applied directly to the rafter eave, it forms a sloping soffit, which creates a pocket that can trap hot air and embers from a wildfire
Figure 2. Wrong - If the soffit is applied directly to the rafter eave, it forms a sloping soffit, which creates a pocket that can trap hot air and embers from a wildfire (Source: CSFS 2012).
Right – In wildfire prone areas, a flat soffit is preferred to an angled soffit that follows the roofline and could trap rising embers from a wildfire; installing the vent on the fascia keeps hot air and embers from fires out of a vented attic
Figure 3. Right – In wildfire prone areas, a flat soffit is preferred to an angled soffit that follows the roofline and could trap rising embers from a wildfire; installing the vent on the fascia keeps hot air and embers from fires out of a vented attic (Source: CSFS 2012).

 

Videos
CAD

Compliance

The Compliance tab contains both program and code information. Code language is excerpted and summarized below. For exact code language, refer to the applicable code, which may require purchase from the publisher. While we continually update our database, links may have changed since posting. Please contact our webmaster if you find broken links.

ENERGY STAR Certified Homes, Version 3/3.1 (Rev. 09)

ENERGY STAR Certified Homes requires that builders comply with the National Water Management System Builder Requirements which specifies water management details for roofs, walls, foundations, sites, and building materials.

Please see the ENERGY STAR Certified Homes Implementation Timeline for the program version and revision currently applicable in in your state.

DOE Zero Energy Ready Home (Revision 07)

Exhibit 1 Mandatory Requirements.
Exhibit 1, Item 1) Certified under the ENERGY STAR Qualified Homes Program or the ENERGY STAR Multifamily New Construction Program.
Exhibit 1, Item 6) Certified under EPA Indoor airPLUS. See the EPA Indoor airPLUS checklist for additional building and site water management requirements.

2009 – 2018 International Energy Conservation Code (IECC) and International Residential Code (IRC)

2018 IRC R301.2.1 Wind design criteria. Buildings shall be constructed in accordance with the wind provisions of this code using the ultimate design wind speed in Table R301.2(1) as determined from Figure R301.2(5)A. Where not otherwise specified, the wind loads listed in Table R301.2(2) adjusted for height and exposure using Table R301.2(3) shall be used to determine design load performance requirements.

Retrofit: 

2009, 2012, 2015, 2018, and 2021 IECC

Section R101.4.3 (Section R501.1.1 in 2015, 2018, and 2021 IECC). Additions, alterations, renovations, or repairs shall conform to the provisions of this code, without requiring the unaltered portions of the existing building to comply with this code. (See code for additional requirements and exceptions.)

2009, 2012, 2015, 2018, and 2021 International Wildland-Urban Interface Code (IWUIC)

Chapter 5 Sections 504, 505, and 506 discuss the requirements for roof assemblies in the wildland-urban interface.

Section 504 Class 1 Ignition-Resistant Construction.

Section 504.10.1 Attic ventilation openings, foundation or underfloor vents, or other ventilation openings in vertical exterior walls and vents through roofs shall not exceed 144 square inches (0.0929 m2) each. Such vents shall be covered with noncombustible corrosion-resistant mesh with openings not to exceed ¼ inch (6.4 mm), or shall be designed and approved to prevent flame or ember penetration into the structure.

Section 504.10.1 Vent locations. Attic ventilation openings shall not be located in soffits, in eave overhangs, between rafters at eaves, or in other overhang areas. Gable end and dormer vents shall be located not less than 10 feet (3048 mm) from lot lines. Underfloor ventilation openings shall be located as close to grade as practical.

Section 505 Class 2 Ignition-Resistant Construction.

Section 505.10.1 Attic ventilation openings, foundation or underfloor vents, or other ventilation openings in vertical exterior walls and vents through roofs shall not exceed 144 square inches (0.0929 m2) each. Such vents shall be covered with noncombustible corrosion-resistant mesh with openings not to exceed ¼ inch (6.4 mm), or shall be designed and approved to prevent flame or ember penetration into the structure.

Section 505.10.1 Vent locations. Attic ventilation openings shall not be located in soffits, in eave overhangs, between rafters at eaves, or in other overhang areas. Gable end and dormer vents shall be located not less than 10 feet (3048 mm) from lot lines. Underfloor ventilation openings shall be located as close to grade as practical.

Note: The IWUIC does not contain any requirements for attic ventilation openings for Class 3 Ignition-Resistant Construction.

2020 Florida Building Code 

Section 1523.6.5.2.13 Ridge vents of metal, plastic or composition material. All ridge vents shall be tested in compliance with TAS 100(A) for wind-driven water infiltration. All ridge ventilators shall be restricted to roof mean height as tested in compliance with TAS 100(A) and shall be listed in the system manufacturer’s product approval. (See code for additional requirements and exceptions.)

 

This Retrofit tab provides information that helps installers apply this “new home” guide to improvement projects for existing homes. This tab is organized with headings that mirror the new home tabs, such as “Scope,” “Description,” “Success,” etc. If there is no retrofit-specific information for a section, that heading is not included.

Existing Homes

The information regarding roof vents that is provided for new homes applies to existing homes as well. When a roof replacement occurs, consider also replacing the roof vents and venting system to vents that may improve ventilation performance and may provide better resistance to local climate conditions, for example replacing mushroom or gable vents with reinforced soffit vents and continuous ridge vents that are designed to minimize wind-borne rain intrusion and lined with metal screening to keep out insects and wind-born embers.

More Info.

Access to some references may require purchase from the publisher. While we continually update our database, links may have changed since posting. Please contact our webmaster if you find broken links.

References and Resources*
Author(s)
Lstiburek
Organization(s)
Building Science Corporation
Publication Date
Description
Document providing background and approach for the prep work necessary prior to adding attic insulation - focusing on combustion safety, ventilation for indoor air quality, and attic ventilation for durability.
Author(s)
Quarles
Organization(s)
Insurance Institute for Business & Home Safety
Publication Date
Description
Report covering the migration of wind-blown embers in roof vents.
*For non-dated media, such as websites, the date listed is the date accessed.
Contributors to this Guide

The following authors and organizations contributed to the content in this Guide.

Building Science Corporation

Pacific Northwest National Laboratory

Last Updated

Mobile Field Kit

The Building America Field Kit allows you to save items to your profile for review or use on-site.

Sign Up  or  Log In

Did you find this information helpful?