Skip to main content

Scope

Install an air barrier behind staircases installed on exterior walls.
Install an air barrier behind staircases installed on exterior walls.

Install an air barrier behind staircases installed on exterior walls.

  • Install insulation without misalignments, compressions, gaps, or voids in exterior wall cavities behind staircases installed along exterior walls.
  • Install a rigid air barrier to prevent wall cavity insulation from sagging and to create a continuous thermal barrier. Rigid air barrier material could include rigid foam insulation, drywall, plywood, or OSB, among others.
  • Seal all seams, gaps, and holes in the air barrier with caulk or foam.
  • Ensure that the air barrier is continuous and in full contact with the insulation.
  • If spray foam insulation is used for the wall cavity insulation, the spray foam can serve as the air barrier if it is at least 5.5 inches thick if open-cell or at least 1.5 inches thick if closed-cell spray foam insulation.  
  • ENERGY STAR requires that an air barrier be installed at the exterior vertical surface of the wall insulation in all climate zones and also that an air barrier be installed at the interior vertical surface in IECC Climate Zones 4-8 (ENERGY STAR).

See the Compliance Tab for links to related codes and standards and voluntary federal energy-efficiency program requirements.

Description

Staircases and staircase landings are often located along exterior walls or walls adjoining unconditioned spaces like garages or attics. Insulating and air blocking of the exterior wall below the stairs is sometimes overlooked. When the insulation in the exterior wall cavities is not fully aligned with (touching) the interior wall sheathing (drywall), the insulation’s effectiveness is reduced. After filling the wall cavities with insulation, the walls should be covered with a rigid air barrier material such as rigid foam insulation, OSB, or drywall that is taped at any seams and sealed to the bottom plate, top plate, and framing at the edges with caulk. The insulation should fill the cavity and be fully aligned with the rigid sheathing.

Staircases may be prefabricated or custom site-built. Prefabricated stairs are often used when the stairs will be covered with carpet, although they can be ordered with hardwood and custom finishes. Custom staircases are sometimes built when the stair treads will be hardwood.

Prefabricated stairs come with the stair treads and risers already attached to the stringer boards. The most common varieties are the notched stringer stair (Figure 1) and the routed stringer stair (Figure 2). The notched staircase uses three stringers that are cut out or notched to hold the stair step treads and risers. Routed stringer stairs use two stringer boards that are not notched. The routed stringer differs from the notched stair by utilizing two visible skirt boards as its structural support stringers. Each stringer is usually a solid finished piece of wood, typically 12 inches high and 1.25 inches thick, that is routed to hold the treads and risers. The steps are nailed and glued to the stringers. Because these stringer boards extend above and below the sides of the steps, they serve as the finish boards as well.

These materials may be installed by insulators, framers, or drywallers. This task should be included in the contract for the appropriate trade depending on the workflow at the specific job site.

Prefabricated notched stringer staircase.
Figure 1. A prefabricated notched stringer staircase comes with the stair step treads and risers already fastened to the three notched stringer boards.

 

Prefabricated routed stringer staircase.
Figure 2. A prefabricated routed stringer staircase comes with the stair step treads and risers already fastened to the two routed stringer boards, which also serve as the finish boards.

 

How to Install a Site-Built or Prefabricated Notched Stringer Staircase on an Exterior Wall

  1. Attach a spacer board to the outer side of the outside notched stringer board on the side that will attach to the wall (Figure 3). Attach the spacer board flush with the bottom edge of the stringer board. The spacer board should be thick enough to allow room to slide the drywall between the stringer and the exterior wall studs. If you want to install a finish board along the steps, use a wider spacer (e.g., a 2x4) that will accommodate the thickness of both the drywall and the finish board.

    Caulk the drywall to the spacer board behind the stringer board.
    Figure 3. Construct and air seal a site-built or prefabricated notched-stringer staircase by caulking the seam between the spacer and the drywall above and below the spacer. (Source: PNNL.)
  2. Attach the stringers at the base floor and the second floor or landing. Insulate the wall. Attach the stringer board to the exterior wall studs through the spacer board. The spacer board will give you room to slide the drywall between the riser and the exterior wall studs. 
  3. Cut drywall to fit from the top of the spacer board to the ceiling. Apply caulk or joint compound along the top of the spacer (or bottom edge of the drywall). Slide the drywall behind the stringer board so it is resting on the spacer board and fasten it to the exterior wall studs (Figure 4). Install a finish board next to the drywall if desired.

    Drywall is installed above the spacer board and drywall or another sheet good is installed below the spacer board to provide an air barrier on the exterior wall below the steps.
    Figure 4. Install drywall above and below a prefabricated routed stringer staircase and caulk the edge of the drywall to the spacer board to air seal a staircase on an exterior wall. (Source: PNNL.)
  4. Below the stairs, apply caulk to the exterior wall framing and the bottom edge of the spacer board then install rigid foam, drywall, or another sheet good from the bottom of the stringer board to the bottom plate of the wall. Caulk or tape any seams.

How to Install a Prefabricated Routed Stringer Staircase

  1. If a prefabricated routed stringer staircase is used, insulate the wall, then attach the bottom end of the stringers to the floor and the top end to the second floor or landing. Fasten the staircase through the stringer boards to the exterior wall studs. Install drywall cut at a diagonal to fit from the top of the stringer/finish board to the ceiling. Apply caulk or joint compound to the seam between the top of the finish board and the drywall (Figure 5). Cover the seam with trim.

    Air sealing behind a staircase.
    Figure 5. Air seal a prefabricated routed stringer staircase by caulking the seam between the drywall and stringer finish board above the staircase and the seam between the stringer and rigid air barrier below the staircase. (Source: PNNL.)
  2. Below the stairs, apply caulk to the exterior wall framing and to the bottom edge of the stringer board, then install rigid foam, drywall, or another sheet good from the bottom of the stringer/finish board to the bottom plate of the wall. Caulk or tape any seams. 

Ensuring Success

The site supervisor should visually inspect the exterior wall underneath staircases or staircase landings located on exterior walls during construction to confirm that the wall cavity is insulated and that a rigid air barrier material is installed on the interior surface of the exterior wall in contact with the cavity insulation. Blower door testing conducted as part of whole-house energy performance testing may help indicate if there are air leaks at staircases. High-performance branding programs and the 2009 and 2012 IECC require that builders meet specified insulation levels and infiltration rates. See the Compliance tab for these specified infiltration rates.

Region

The map in Figure 1 shows the climate zones for states that have adopted energy codes equivalent to the International Energy Conservation Code (IECC) 2009, 12, 15, and 18. The map in Figure 2 shows the climate zones for states that have adopted energy codes equivalent to the IECC 2021. Climate zone-specific requirements specified in the IECC are shown in the Compliance Tab of this guide. 

Figure 1. Climate Zone Map from IECC 2009, 12, 15, and 18.
Figure 1. Climate Zone Map from IECC 2009, 12, 15, and 18. (Source: 2012 IECC)

 

Climate Zone Map from IECC 2021.
Figure 2. Climate Zone Map from IECC 2021. (Source: 2021 IECC)

 

Training

Right and Wrong Images

Right – Insulation properly installed before air barrier
Right – Insulation properly installed before air barrier
Right – Insulation properly installed before air barrier
Source
Author(s)
U.S. Environmental Protection Agency,
ENERGY STAR
Organization(s)
EPA
Description

Guide describing details that serve as a visual reference for each of the line items in the Thermal Enclosure System Rater Checklist.

Wrong –  No air barrier installed under staircase
Wrong – No air barrier installed under staircase
Wrong – No air barrier installed under staircase
Source
Author(s)
U.S. Environmental Protection Agency,
ENERGY STAR
Organization(s)
EPA
Description

Guide describing details that serve as a visual reference for each of the line items in the Thermal Enclosure System Rater Checklist.

Right – Air barrier installed under staircase (picture taken from house looking into attached garage)
Right – Air barrier installed under staircase (picture taken from house looking into attached garage)
Right – Air barrier installed under staircase (picture taken from house looking into attached garage)
Source
Author(s)
U.S. Environmental Protection Agency,
ENERGY STAR
Organization(s)
EPA
Description

Guide describing details that serve as a visual reference for each of the line items in the Thermal Enclosure System Rater Checklist.

Wrong – No air barrier installed under staircase
Wrong – No air barrier installed under staircase
Wrong – No air barrier installed under staircase
Source
Author(s)
U.S. Environmental Protection Agency,
ENERGY STAR
Organization(s)
EPA
Description

Guide describing details that serve as a visual reference for each of the line items in the Thermal Enclosure System Rater Checklist.

Wrong - The air barrier is not sealed (picture taken from garage looking into house).
Wrong - The air barrier is not sealed (picture taken from garage looking into house).
Wrong - The air barrier is not sealed (picture taken from garage looking into house).
Source
Author(s)
U.S. Environmental Protection Agency,
ENERGY STAR
Organization(s)
EPA
Description

Guide describing details that serve as a visual reference for each of the line items in the Thermal Enclosure System Rater Checklist.

More Info

References and Resources

Publication Date
·
Author(s)
U.S. Environmental Protection Agency,
ENERGY STAR
·
Organization(s)
EPA
Description
Guide describing details that serve as a visual reference for each of the line items in the Thermal Enclosure System Rater Checklist.

*For non-dated media, such as websites, the date listed is the date accessed.

Contributors to this Guide

The following authors and organizations contributed to the content in this Guide.

Sales

Building Science-to-Sales Translator

Fully Aligned Air Barriers = Whole-House Draft Barrier

Image(s)

Technical Description

A whole-house draft barrier is a continuous layer of air-tight materials that block air leaks. This barrier can be integrated with other materials to also function as a water barrier, thermal barrier, and vapor barrier. For example, rigid foam insulation can be used to block thermal flow as well as air flow when seams are sealed with tape, caulk, adhesives, or liquid-applied sealants. Some rigid foams have an integrated water control layer as well. Additionally, drywall can serve as an interior air barrier when the seams are taped and spackled, and caulk, spray foam, or gaskets are used to seal around wiring, plumbing, and other penetrations. It also serves as the vapor barrier when finished with paint. Insulation should be in full contact with the air barrier layer.

Whole-House Draft Barrier
Sales Message

Whole-house draft barriers block air flow that can undermine the thermal protection with a complete high-performance insulation system. What this means to you is less wasted energy along with enhanced comfort, quiet, and durability. Wouldn’t you agree it would be a shame to only get a partial return on your investment in advanced insulation?

Last Updated

Questions? Comments? Contact our webmaster.

Disclaimer

This content is a work created with funding provided by the United States Department of Energy under Contract no DE-AC05-076RL01830 for the operation of Pacific Northwest National Laboratory. The information and guidance provided by Pacific Northwest National Laboratory (PNNL) in the content are intended solely for educational purposes only and do not constitute formal training or certification. It is provided with the explicit understanding that neither the United States Government nor the United States Department of Energy, nor the Contractor, nor any or their employees, nor any jurisdiction or organization that has cooperated in the development of these materials, makes any warranty, express or implied, or assumes any legal liability or responsibility for the accuracy, completeness, or usefulness or any information, apparatus, product, software, or process disclosed, or represents that its use would not infringe privately owned rights. Reference herein to any specific commercial product, process, or service by trade name, trademark, manufacturer, or otherwise does not constitute or imply its endorsement, recommendation, or favoring by the United States Government or any agency thereof, or Battelle Memorial Institute. The views and opinions of authors expressed herein do not necessarily state or reflect those of the United States Government or any agency thereof. Viewers assumes full responsibility for all actions that they may take from information provided in this content including ensuring the safety, code compliance, and proper functionality of any products they choose to install. Installation and use of such products should be performed in accordance with local regulations and manufacturer instructions.