Insulating Heated Garage Plenums in Multifamily Buildings

    Scope
    Scope Images
    Image
    Heated recirculation plenum spaces can be installed in parking garages in cold climates to prevent pipes from freezing and warm the floor of occupied space directly above the garage.
    Scope

    Heated recirculation plenum spaces can be installed in parking garages in cold climates to prevent pipes from freezing and warm the floor of occupied space directly above the garage. 

    • If heated plenum spaces are included in a parking garage, ensure that the sides of the plenum space are insulated and have an air barrier that is fully aligned with the insulation.
    • Ensure that all service penetrations through the garage slab are properly air sealed. 
    • Ensure that there is an opening to access the interior of the plenum space for any necessary repairs or maintenance. 
    • If the top of the heated plenum is insulated, ensure that the insulation at the top of the plenum meets or exceeds IECC insulation requirements and that the insulation is aligned with an air barrier. 
    • If only the bottom of the heated plenum is insulated, ensure that the insulation at the bottom of the plenum meets or exceeds IECC insulation requirements and that the insulation is aligned with an air barrier. 

    See the Compliance Tab for links to related codes and standards and voluntary federal energy-efficiency program requirements.

    Description
    Description

    In cold climates, the freezing of pipes that run through garage spaces is a common concern. Occupant comfort in dwelling units directly above the garage is also a concern because the slab between the garage and the conditioned space above can get cold even with adequate insulation. Heated recirculation plenum spaces can be installed in the garage to keep pipes warm and heat the underside of the slab between the garage and the conditioned space above. 

    Heated recirculation plenum spaces in garages are insulated dropped ceiling spaces that are located between the garage and conditioned space above, and are equipped with plenum heaters that provide both heat and air circulation to the plenum space. The plenum heaters are typically equipped with controls and will shut down when the temperature inside the garage plenum space exceeds 40°F.

    Unlike supply and return plenum spaces, recirculation plenum spaces do not transport air that is supplied to or exhausted from spaces; instead, air is recirculated within the plenum space. As a result, there is usually little to no pressure difference between the plenum space and adjacent spaces, leading to limited or insignificant air leakage into and out of the plenum space. However, it should be noted that it is not recommended to install heated garage plenums in IECC Climate Zones 3 and lower due to concerns of upward vapor drive during cooling seasons. 

    In buildings with heated garage plenums, the floor between the garage and conditioned occupied space above must be insulated per IECC requirements. 

    Note that with both approaches, the following should also be ensured: 

    • The sides of the plenum space are insulated, and an air barrier is fully aligned with the insulation along the sides. 
    • Any service penetrations through the garage slab should be air sealed. 
    • There is an opening to access the interior of the plenum space for any necessary repairs or maintenance. This can be achieved using lay-in ceiling tiles, which are typically insulated with fiberglass or mineral wool batt insulation (Figure 3). 

    There are two approaches to meeting ENERGY STAR Multifamily New Construction requirements for heated garage plenums. 

    • Insulate the bottom of the plenum space (Figure 1). In this case, the insulation at the bottom of the plenum must meet or exceed IECC insulation requirements and should be fully aligned with an air barrier. 
    • Insulate both the bottom and the top of the plenum space (Figure 2). In this case, the insulation at the top of the plenum space must meet or exceed IECC insulation requirements and should be fully aligned with an air barrier. With this approach, ENERGY STAR Multifamily New Construction requires that the insulation at the bottom of the plenum space is R-13 or greater. 
    Image
    This heated garage plenum is insulated along the bottom and sides, and the insulation is fully aligned with an air barrier. The insulation at the bottom of the plenum space meets IECC insulation requirements.
    This heated garage plenum is insulated along the bottom and sides, and the insulation is fully aligned with an air barrier. The insulation at the bottom of the plenum space meets IECC insulation requirements.
    This heated garage plenum is insulated along the bottom and sides, and the insulation is fully aligned with an air barrier. The insulation at the bottom of the plenum space meets IECC insulation requirements.
    Figure 1. This heated garage plenum is insulated along the bottom and sides, and the insulation is fully aligned with an air barrier. The insulation at the bottom of the plenum space meets IECC insulation requirements (Source: Building Science Corporation).
    Image
    This heated garage plenum space is insulated along its top, bottom and sides, and the insulation at the top of the plenum meets IECC requirements. The insulation along the top and sides is fully aligned with an air barrier.
    This heated garage plenum space is insulated along its top, bottom and sides, and the insulation at the top of the plenum meets IECC requirements. The insulation along the top and sides is fully aligned with an air barrier.
    This heated garage plenum space is insulated along its top, bottom and sides, and the insulation at the top of the plenum meets IECC requirements. The insulation along the top and sides is fully aligned with an air barrier.
    Figure 2. This heated garage plenum space is insulated along its top, bottom and sides, and the insulation at the top of the plenum meets IECC requirements. The insulation along the top and sides is fully aligned with an air barrier (Source: Building Science Corporation).
    Image
    Drop-in ceiling assemblies consisting of suspended ceiling tiles (common in multifamily buildings) are often insulated with fiberglass or mineral wool batt insulation.
    Drop-in ceiling assemblies consisting of suspended ceiling tiles (common in multifamily buildings) are often insulated with fiberglass or mineral wool batt insulation.
    Drop-in ceiling assemblies consisting of suspended ceiling tiles (common in multifamily buildings) are often insulated with fiberglass or mineral wool batt insulation.
    Figure 3. The ceiling tiles typically used for drop-in ceiling assemblies are often insulated with fiberglass or mineral wool batt insulation (Source: Building Science Corporation).

    Air gaps within walls are a concern due to the large vertical height that can lead to significant convection forces. However, airflow is generally not a concern within garage plenums, as the convection forces are small due to a limited vertical distance within the dropped ceiling (Figure 4).

    Image
     Airflow within drop-in ceiling assemblies is generally not a concern due to the limited vertical height. However, airflow within air gaps in walls is a concern due to the much larger vertical height.
    Airflow within drop-in ceiling assemblies is generally not a concern due to the limited vertical height. However, airflow within air gaps in walls is a concern due to the much larger vertical height.
    Airflow within drop-in ceiling assemblies is generally not a concern due to the limited vertical height. However, airflow within air gaps in walls is a concern due to the much larger vertical height.
    Figure 4. Airflow within drop-in ceiling assemblies is generally not a concern due to the limited vertical height. However, airflow within air gaps in walls is a concern due to the much larger vertical height (Source: Building Science Corporation).

    In cases where a garage plenum space is adjacent to a separately cast garage slab without a plenum space, adding rigid insulation as a thermal break between the garage slabs can reduce thermal bridging and energy loss (Figure 5). For more information, see the guide on Reducing Thermal Bridging in Mass and Steel Framed Multifamily Buildings. 

    Image
    Rigid insulation can be used as a thermal break between a garage slab with a heated plenum space and a separately cast garage slab without a heated plenum space.
    Rigid insulation can be used as a thermal break between a garage slab with a heated plenum space and a separately cast garage slab without a heated plenum space.
    Rigid insulation can be used as a thermal break between a garage slab with a heated plenum space and a separately cast garage slab without a heated plenum space.
    Figure 5. Rigid insulation can be used as a thermal break between a garage slab with a heated plenum space and a separately cast garage slab without a heated plenum space (Source: Building Science Corporation).
    Climate
    Climate

    Since upward vapor drive during the cooling season is a concern in hot, humid climates, it is not recommended to install heated garage plenums in IECC Climate Zones 3 and lower. The figures below can be used to determine your climate zone. The map in Figure 1 shows the climate zones for states that have adopted energy codes equivalent to the International Energy Conservation Code (IECC) 2009, 12, 15, and 18. The map in Figure 2 shows the climate zones for states that have adopted energy codes equivalent to the 2021 IECC.

    Image
    IECC climate zone map
    IECC climate zone map
    IECC climate zone map
    Figure 1. Climate Zone Map from IECC 2009, 12, 13, and 18 (Source: 2021 IECC).
    Image
    Climate Zone Map from IECC 2021
    Climate Zone Map from IECC 2021
    Climate Zone Map from IECC 2021
    Figure 2. Climate Zone Map from IECC 2021 (Source: 2021 IECC).

    Where garage plenums are installed, they must meet IECC insulation requirements. See the Compliance Tab for climate-specific insulation requirements in the IECC.

    Training
    Right and Wrong Images
    Image
    Right - The service penetrations through the structural slab in this garage plenum are air sealed.
    Right - The service penetrations through the structural slab in this garage plenum are air sealed.
    Image
    Right - This heated garage plenum is insulated and has an opening to access the interior, allowing for repairs and maintenance.
    Right - This heated garage plenum is insulated and has an opening to access the interior, allowing for repairs and maintenance.
    Image
    Right - This heated garage plenum has insulated ceiling tiles.
    Right - This heated garage plenum has insulated ceiling tiles.
    Image
    Right - This heated garage plenum is insulated along the bottom of the plenum space.
    Right - This heated garage plenum is insulated along the bottom of the plenum space.
    Compliance
    More

    More Info.

    Access to some references may require purchase from the publisher. While we continually update our database, links may have changed since posting. Please contact our webmaster if you find broken links.

    References and Resources*
    Author(s)
    Lstiburek Joseph W
    Organization(s)
    Building Science Corporation,
    BSC
    Publication Date
    Description
    Article Describing methods for thermally isolating multifamily parking garages.
    Author(s)
    U.S. Environmental Protection Agency
    Organization(s)
    EPA
    Publication Date
    Description
    This publication provides a set of best practices for improving indoor air quality in conjunction with energy upgrade work in homes.
    Author(s)
    U.S. Environmental Protection Agency
    Organization(s)
    EPA
    Publication Date
    Description
    Document providing an overview of the Thermal Bypass Checklist for the ENERGY STAR Qualified Homes program.
    Author(s)
    Lstiburek Joseph W
    Organization(s)
    Building Science Corporation,
    BSC
    Publication Date
    Description
    Information sheet providing definitions, applications, and techniques for applying air barriers.
    *For non-dated media, such as websites, the date listed is the date accessed.
    Contributors to this Guide

    The following authors and organizations contributed to the content in this Guide.

    Building Science Corporation, lead for the Building Science Consortium (BSC), a DOE Building America Research Team.

    Pacific Northwest National Laboratory

    Last Updated

    Did you find this information helpful?

    If you have questions and/or would like a reply to this feedback, please include your e-mail address in the message.
    This question is for testing whether or not you are a human visitor and to prevent automated spam submissions.