Skip to main content

ECM Air Handler Fans

    Scope
    Scope Images
    Image
    ECM Motor and Control
    Scope

    Choose central air handler based HVAC equipment that uses a fan powered by

    • An electronically commutated (ECM) motor
    • Not a split capacitor motor

       

    See the Compliance Tab for related codes and standards requirements, and criteria to meet national programs such as DOE’s Zero Energy Ready Home programENERGY STAR Single-Family New Homes, and Indoor airPLUS.

     

    Description
    Description

    Home owners who use an HVAC system with a central air handler fan can realize significant energy savings by using a fan with an electronically commutated (ECM) motor (see Figure 1).

    ECM Motor and Control
    Figure 1. ECM Motor and Control

    Savings will be even larger for homeowners who run the HVAC fan continuously or frequently to filter the air or to bring in and circulate fresh air as part of a whole-house ventilation system. Because they are variable speed and can adjust their speed up or down to meet load, ECMs can operate on as little as 80 watts of electricity. In contrast, permanent split capacitor (PSC) engines are single-speed motors that typically consume between 500 and 550 watts when providing heating and cooling (Michael 2009).

    Until recently PSC motors have been the most popular fan motor for furnaces, air handlers, condensing units, and packaged units (see Figure 2).

    PSC Motor
    Figure 2. PSC Motor

    They are known for their simplicity, reliability, and low cost. However, these alternating current (AC) induction motors have inherent inefficiencies; they are at best 60% efficient and they generate excess heat which must be dealt with. PSC motors are not programmable and their motor speed cannot be easily varied.

    ECM technology is based on a direct current (DC) design that is inherently about 80% efficient, compared to the 60% efficiency of a PSC motor, and they run cooler than PSC motor designs (Holliday 2011). The brushless design eliminates failures caused by worn brushes and commutators (see Figure 3).

    ECM Motor
    Figure 3. ECM Motor

    ECM fans use about 400 watts in cooling mode and about 80 in continuous fan mode (Michael 2009). Because of their variable speed, they can run at low speeds for much of the time while PSC motors are typically on high speed all the time, so annual operating costs for ECMs can be 25% to 75% lower (Minnesota Power 2015).

    The ability of ECMs to ramp up and ramp down slowly adds to their quiet operation and enhances their dehumidifying ability, especially when combined with a two-stage compressor and dehumidification controls. In dry climates, the ECM motor can be programmed for cooling at high speed followed by continued running of the fan at the end of the cooling cycle at a lower speed and watt draw to evaporate the water off the coil. In a wet climate, the controls are set differently for lower speed cooling, which provides more dehumidification in cooling mode, with the fan going off at the end of the compressor cycle to allow the coil to drain. Even when the system is set to “constant fan,” the fan still shuts down for 20 minutes at the end of the compressor cycle so the coil can drain. In climates that are sometimes dry and sometimes wet, an indoor thermidistat can be installed that will enable the motor controls to switch from dry climate programming to wet climate programming depending on the indoor conditions (Holliday 2011).

    New HVAC equipment with ECMs installed typically costs 40% to 60% more than non-ECM based equipment (Michael 2009). Building America researchers note that ECM motors can reduce fan energy consumption by 50% or more over PSCs as long as the duct system is properly installed and constructed to eliminate excessive airflow resistance (Rudd 2011).

    Both the IECC 2012 and the ENERGY STAR Certified Homes program require the use of an ECM fan motor if the home’s HVAC air handler will be used to distribute fresh air as part of a whole-house ventilation system. See the guide Whole House Ventilation Strategies for Existing Homes for more information. Alternately, ENERGY STAR permits non-ECM fan motors if the HVAC system has controls that will reduce the stand-alone ventilation run-time by accounting for hours when the HVAC system is heating or cooling while meeting code-required ventilation levels, such as those specified in ASHRAE Standard 62.2-2010/2013, Ventilation for Acceptable Indoor Air Quality in Low-Rise Residential Buildings. See manufacturers’ instructions for installing and setting the timer, damper, and controls. 

    Figure 4 shows a central-fan-integrated ventilation system that uses the air handler fan to distribute fresh air ducted directly to the return side of the air handler from outside. When the central air handler fan uses an ECM motor, the motor power draw will be about one-fourth of what it would be with a PSC motor when the system is operating in “fan-only” mode for ventilation.

    Using an ECM motor rather than a PSC motor in air handler fan used for central fan integrated ventilation can cut fan energy use by 25% to 75%.
    Figure 4. Using an ECM motor rather than a PSC motor in air handler fan used for central fan integrated ventilation can cut fan energy use by 25% to 75%.

     

    Success
    Ensuring Success

    Specify high-performance HVAC equipment that includes an electronically commutated (ECM) fan motor.

    If the whole-house ventilation system uses the HVAC central air handler, then the fan motor should be a variable speed electronically commutated motor (ECM) or an integral control motor (ICM) that includes a controller (e.g., a smart cycler) that reduces the ventilation run time by accounting for hours when the HVAC system is already operating the fan for heating or cooling the home.

    Climate
    Climate

    No climate-specific guidance is provided.

    Training
    Right and Wrong Images
    Image
    ECM Motor and Control
    ECM Motor and Control
    Image
    ECM Motor with Integral Control
    ECM Motor with Integral Control
    Image
    ECM Motor Retrofit
    ECM Motor Retrofit
    Videos
    Publication Date
    Author(s)
    Advanced Technology Institute (ATI)
    Organization(s)
    Advanced Technology Institute (ATI)
    Description
    Video describing permanent split capacitor (PSC) motors.
    Compliance

    Compliance

    The Compliance tab contains both program and code information. Code language is excerpted and summarized below. For exact code language, refer to the applicable code, which may require purchase from the publisher. While we continually update our database, links may have changed since posting. Please contact our webmaster if you find broken links.

     

    ENERGY STAR Single-Family New Homes, Version 3/3.1 (Rev. 11)

    National Rater Field Checklist
    HVAC System.
    7. Dwelling Unit Mechanical Ventilation Systems (“Vent System”) 45 & Inlets In Return Duct 46
    7.5 If Vent System controller operates the HVAC fan, then HVAC fan operation is intermittent and either the fan type is ECM / ICM or the controls will reduce the run-time by accounting for HVAC system heating or cooling hours. 52

    Footnote 45) As defined by ANSI / RESNET / ICC Std. 301-2019, a Dwelling Unit Mechanical Ventilation System is a ventilation system consisting of powered ventilation equipment such as motor-driven fans and blowers and related mechanical components such as ducts, inlets, dampers, filters and associated control devices that provides dwelling-unit ventilation at a known or measured airflow rate.

    Footnote 46) Item 7.3 applies to any outdoor air inlet connected to a ducted return of the dwelling unit HVAC system, regardless of its intended purpose (e.g., for ventilation air, make-up air, combustion air). This Item does not apply to HVAC systems without a ducted return.

    Footnote 52) Note that the ‘fan-on’ setting of a thermostat would not be an acceptable controller because it would continuously operate the HVAC fan.

    Please see the ENERGY STAR Single-Family New Homes Implementation Timeline for the program version and revision currently applicable in in your state.

     

    DOE Zero Energy Ready Home (Revision 07)

    Exhibit 1 Mandatory Requirements.
    Exhibit 1, Item 1) Certified under the ENERGY STAR Qualified Homes Program or the ENERGY STAR Multifamily New Construction Program.
    Exhibit 1, Item 6) Certified under EPA Indoor airPLUS.

     

    EPA Indoor airPLUS (Revision 04)

    The U.S. Environmental Protection Agency (EPA) Indoor airPLUS Construction Specifications requires homes to meet the ENERGY STAR Certified Homes requirements. Additional advisories include the following.

    4.5 Mechanical Whole-House Ventilation. Advisory: Outdoor air ducts connected to the return side of an air handler should be used as supply ventilation only if the manufacturers’ requirements for return air temperature are met (e.g., most manufacturers recommend a minimum of 60 degrees Fahrenheit air flow across furnace heat exchangers). EPA also recommends filtering air inlets with a filter rated at MERV 13 or higher to minimize outdoor particles entering the home.

     

    2009 International Energy Conservation Code (IECC) 
    Section 403.5 Mechanical ventilation (Mandatory). Automatic or gravity dampers are installed on all outdoor air intakes and exhausts.

    2012 IECC 
    R403.5 Mechanical ventilation (Mandatory). The building must have ventilation that complies with the International Residential Code or International Mechanical Code. Outdoor air intakes and exhausts must have automatic or gravity dampers that close when the ventilation system is not operating.

    R403.5.1 Whole-House mechanical ventilation system fan efficacy. Mechanical ventilation system fans should meet the fan efficacy requirements shown in IECC Table R403.5.1. Exception: Where mechanical ventilation fans are part of the tested and listed HVAC equipment, they should be powered by an electronically commutated motor.

    20152018, and 2021 IECC
    R403.6 Mechanical ventilation (Mandatory). The building must have ventilation that complies with the International Residential Code or International Mechanical Code. Outdoor air intakes and exhausts must have automatic or gravity dampers that close when the ventilation system is not operating.

    R403.6.1 (R403.6.2 in 2021 IECC) Whole-House mechanical ventilation system fan efficacy. Mechanical ventilation system fans should meet the fan efficacy requirements shown in IECC Table R403.6.1 (R403.6.2 in 2021 IECC). Exception: Where mechanical ventilation fans (air handlers in 2018 IECC) are part of the tested and listed HVAC equipment, they should be powered by an electronically commutated motor.

    Retrofit:  2009, 2012, 2015, 2018,  and 2021 IECC

    Section R101.4.3 (in 2009 and 2012). Additions, alterations, renovations, or repairs shall conform to the provisions of this code, without requiring the unaltered portions of the existing building to comply with this code. (See code for additional requirements and exceptions.)

    Chapter 5 (in 2015, 2018, 2020). The provisions of this chapter shall control the alteration, repair, addition, and change of occupancy of existing buildings and structures.

     

    American Society of Heating, Refirgeration and Air Conditioning Engineers (ASHRAE) 62.2-2010, ASHRAE 62.2-2013, and ASHRAE 62.2-2016
    Ventilation for Acceptable Indoor Air Quality in Low-Rise Residential Buildings. This ventilation standard by the American Society of Heating, Air-Conditioning and Refrigeration Engineers (ASHRAE) defines methods for determining the minimum levels of ventilation needed to provide acceptable indoor air quality in low-rise residential buildings.

     

    Air Conditioning Contractors of America (ACCA) Manual S
    Size the heating and cooling equipment including the HVAC fan in accordance with the guidelines described in ACCA Manual S, Residential Equipment Selection.

     

    ACCA Manual J
    Perform building heating and cooling load calculations as described in ACCA Manual J, Residential Load Calculation.

    Retrofit
    Existing Homes

    Inexpensive replacement ECM motors can be installed to replace PSC motors in existing equipment while offering many of the benefits of ECMs, including high efficiency, variable speed, and quiet operation, at a lower cost.

    Home owners may consider replacing just the PSC motor rather than the whole furnace or heat pump, if the motor fails prematurely. (Motor-only replacement  is not recommended if the system is more than 10 years old per Michael 2009). PSC motors typically fail in one of three ways: the bearings, the capacitor, or the windings. A PSC that has seized will be obvious – it can’t be turned by hand, or it will be clearly noisy, ratchety, or resistant. A multi-meter can be used to identify the other two situations. One company offers a troubleshooting tip sheet for testing PSC capacitors and windings (this example is an oil burner motor).

    Comfort improvements alone may warrant replacing a PSC motor with an ECM. Homeowners often appreciate the quiet operation, controllability and improved thermal comfort in part-load situations afforded by an ECM.

    Energy savings can also be significant. In some cases, energy savings may cover the cost of a replacement ECM in just a few years, arguing for the change even before a PSC has failed. This may be true in a climate where the fan is blowing most days of the year or when a central HVAC system is used to distribute ventilation air, increasing fan run time. For example, one utility estimated that motor replacement with an ECM offered a less than 3-year simple payback and over $700 in operating cost savings over a 10-year period. ECM upgrades for fans and pumps sometimes qualify for local utility energy rebates. Check your utility’s website or the DOE Database of State Incentives for Renewables & Efficiency. In some temperate climate zones, the savings from an ECM motor may not justify the added cost. In this case an upgrade might still be justified for noise and comfort improvements. Table 1 outlines some of the differences between PSC motors and ECMs.

    Table 1.  ECM vs PSC Motors

    ATTRIBUTE

    PSC

    ECM

    Expected lifespan

    40,000 to 50,000 hrs. (about 5 yrs)

    90,000 hrs. (about 10 yrs) 

    Cost

    typical

    40-60% premium over PSC; generally short payback period of < 3 yrs

    Noise

    more

    Less due to soft start, variable speeds

    Comfort

    Single speed can result in stagnation or draft due to cycling

    Meets comfort at part load with varying flows to match demand, per furnace capabilities

    Efficiency

    Less than 60%

    Up to 80%

    Controllability

    One to three defined speeds; can’t effectively or efficiently support ventilation

    Variable speeds, can be programmed to achieve additional comfort goals, such as:

    Arid locations - high speed for cooling, followed by low speed to evaporate moisture off the cooling coils to re-humidify air

    Humid locations - reduced-velocity air flow to improve dehumidification

    Other

     

    Sometimes local utilities offer tax credits or rebates; ECMS run cooler than PSCs, dumping less heat to the space

    If considering a motor replacement, don’t ignore systemic problems such as leaky, kinked, or undersized duct systems. Adding an ECM motor to a leaky or poorly balanced system may actually increase energy use and noise, since the motor will ramp up to overcome the distribution inadequacies. Duct systems with an overly high pressure drop (e.g., more than 1-inch water column static pressure) have been shown to cause ECM motors to burn out and fail prematurely. While a PSC motor will stop pushing if the pressure is too high, an ECM will continue to work harder to push air through, wasting energy and eventually burning out. Take into account the size and condition of the current ducts when considering the energy saving potential of replacing a PSC engine with an ECM (Rudd 2011) and always repair ductwork (seal gaps, straighten kinks, balance the entire system) before investing in an ECM upgrade. 

    More

    More Info.

    Access to some references may require purchase from the publisher. While we continually update our database, links may have changed since posting. Please contact our webmaster if you find broken links.

    References and Resources*
    Author(s)
    Holiday,
    Martin
    Organization(s)
    Green Building Advisor
    Publication Date
    Description
    Article in Energy Design Update describing the cost and savings benefits of electronically commutated motors (ECMs) for HVAC equipment.
    Author(s)
    Holliday,
    Martin
    Organization(s)
    Green Building Advisor
    Publication Date
    Description
    Blog post in Green Building Advisor describing the differences between PSC and ECM motors for HVAC fans.
    Author(s)
    Michael,
    Brian
    Organization(s)
    Johnson Controls,
    Inc.
    Publication Date
    Description
    Article in the Air Conditioning, Heating and Refrigeration NEWS newsletter describing PSC, ECM, and ECM replacement motors for HVAC equipment.
    Author(s)
    Mohalley Christopher
    Organization(s)
    Air Conditioning Heating and Refrigeration News,
    ACHR News
    Publication Date
    Description
    Article describing benefits of ECM motors and how they can be installed as retrofit motors in HVAC equipment.
    Author(s)
    Anesi Jen
    Organization(s)
    Air Conditioning Heating and Refrigeration News,
    ACHR News
    Publication Date
    Description
    Article describing how replacing permanent split capacitor (PSC) motors with electronically commutated motors (ECM) can boost bottom line for HVAC contractors as well as improve customer comfort and satisfaction.
    Author(s)
    Aldrich Robb,
    Williamson Jim
    Organization(s)
    Consortium for Advanced Residential Buildings,
    CARB,
    Steven Winter Associates,
    SWA,
    National Renewable Energy Laboratory,
    NREL,
    U.S. Department of Energy,
    DOE
    Publication Date
    Description
    Report detailing the effects of replacing PSC motors with more efficient, variable-speed motors.
    Author(s)
    Mohalley Christopher
    Organization(s)
    Genteq,
    Regal Beloit,
    Regal Rexnord
    Publication Date
    Description
    Presentation describing the history of ECM motors, an overview of ECM motor technology, and a lesson on the installation of ECM motors.
    Author(s)
    Office of Research Facilities
    Organization(s)
    ORF
    Publication Date
    Description
    Bulletin describing the components of ECM motors and comparing their efficiency with PSC motors.
    *For non-dated media, such as websites, the date listed is the date accessed.
    Last Updated

    Did you find this information helpful?

    If you have questions and/or would like a reply to this feedback, please include your e-mail address in the message.
    This question is for testing whether or not you are a human visitor and to prevent automated spam submissions.