Duct to boot connection of jump duct not fastened and sealed
Ducts are insulated but strapping is compressing the insulation therefore reducing the R-value
Ducts sagging because supports not installed at regular intervals
Electronically controlled dampers allow this central air system to provide zoned heating and cooling to specific parts of the home.
Example of an HVAC installer’s balancing report form
Fan housing was oriented in the correct direction to allow proper exhaust duct installation
Fans from seperate dwellings exhausted together without back-draft dampers and not sealed
Fiberglass mesh tape is installed around a duct boot in preparation for air sealing with mastic
Flexible ducts in unconditioned space not installed in cavities smaller than outer duct diameter; in conditioned space not installed in cavities smaller than inner duct diameter
Flexible ducts supported at intervals as recommended by mfr. but at a distance ≤ 5 ft
Hand tools for cutting fiber board sheets include a knife, straight edge, and color-coded edge-cutting tools
HVAC ducts, cavities used as ducts, and combustion inlets and outlets may pass perpendicularly through exterior walls but shall not be run within exterior walls unless at least R-6 continuous insulation is provided on exterior side of the cavity
If HVAC duct must be installed in an exterior wall, separate it from the exterior with at least R-6 of continuous rigid insulation
Inadequate amount of insulation installed with compression, misalignment, and voids
Install supply registers in floors or ceilings to avoid routing ducts through exterior walls
Manual D details show duct size and chase path