Skip to main content

Sealed and Insulated Metal Ducts

    Scope
    Scope Images
    Image
    Air seal and insulate flex ducts
    Scope

    Air-seal and insulate metal ducts.

    • Design a compact duct layout with short straight runs and minimal bends. Design the home to include ducts within conditioned space if possible. (The DOE Zero Energy Ready Home program requires that heating/cooling system supply ducts be installed within the conditioned space of the home.)
    • Install the metal ducts. Use screws to secure connections. Wipe ducts to ensure they are clean and dry especially at seams and joints.
    • Seal all seams and joints in the ducts with mastic. Cover all seams that are wider than 1/8 inch with fiberglass mesh tape then apply mastic.
    • Install duct blanket insulation that is covered with a foil or plastic vapor barrier over the ducts. Overlap blanket by 2 inches and staple. Seal insulation blanket seams with mastic or UL-181 metal tape and mastic.
    • Insulate all supply and return ducts located in unconditioned space. Meet code or program minimum R-value requirements. See the Compliance tab for R-value minimum requirements specified in the IRC, IECC, DOE Zero Energy Ready Home program, and ENERGY STAR criteria.
    • Ensure that all duct connections and seams are air sealed for the following, regardless of whether they are located in conditioned or unconditioned space:
      • supply ducts (connections to boots, trunk ducts, other ducts, i.e., duct splicing);
      • return ducts (connections to return box);
      • ventilation ducting (connections to exhaust fans, for ERV/HRV dedicated ducts)
      • pressure balancing (connections for jump ducts, dedicated returns).
    • Ensure that insulation completely covers ducts and connections without gaps, voids, or compressions.
    • Consider insulating all metal ductwork located in conditioned space, including supply and return ducts, duct boots, and exhaust ducts, to minimize condensation.

    See the Compliance Tab for links to related codes and standards and voluntary federal energy-efficiency program requirements.

    Description
    Description

    Ideally ducts should be located in conditioned space, such as within a dropped ceiling, between floors, in an insulated basement or crawlspace, or in an unvented attic that is insulated along the roof line. If ducts are located in an unconditioned space, such as a vented attic or vented crawlspace, they should be sealed and insulated to prevent heat loss due to air leaks and conduction and to provide some protection against harsh conditions.

    Sealing

    Duct leakage is a double hit on the utility bill: 1) duct leaks are an uncontrolled loss of conditioned air to the outdoors and 2) duct leakage drives building infiltration. For example, if a home had a 2.5-ton (30,000 BTU/H) cooling system moving 1,000 CFM (cubic feet per minute) of air and the ducts had 10% leakage (which is typical in code-built homes), the leakage rate would be 100 CFM. Each cubic foot of air carries with it 30 BTUs/H, so 3,000 BTUs of conditioned air would be lost to the outdoors each hour.

    Duct leakage is an infiltration driver; it can negatively or positively pressurize the house depending on where the ducts are leaking, pulling outside air in through cracks in the building envelope or pushing conditioned air out. If the duct leakage is in the supply-side ducts, the house will be negatively pressurized compared to outdoors. If all the leakage is on the return side, the building will be positive with respect to outdoors. The field technician should understand this concept to help accurately diagnose the dominant sources of duct leakage.

    Insulation

    Whenever ductwork is located in unconditioned spaces, thermal insulation with a vapor barrier is a must to prevent unnecessary heat gain or loss through the duct walls and to prevent condensation from forming on the ducts themselves. For the insulation to work properly, it must be fully aligned and in contact with the walls of the duct system. A typical vented attic with a dark shingle roof can reach summer temperatures of 140ºF. At the same time, the dew point temperature in the attic will be about the same as it is outdoors. In humid climates "duct sweating" can become a significant problem if the ducts’ thermal and vapor barriers are not properly aligned along the entire length of the ducts.

    Metal ductwork is constructed using sheets of galvanized steel. Metal ducts are either rectangular or round in shape. Metal ducting consists of straight lengths, elbows, connectors, junction boxes, and register boots that are purchased or fabricated in the HVAC contractor’s shop and fitted together at the job site. A compact duct layout design with short, straight runs and minimal bends provides the best performance from an air flow standpoint and also reduces the number of lengths and seams that need to be sealed and insulated.

    For more on duct layout, see No Kinks or Sharp Bends in Flex Duct Installation.

    Duct installation standards and installation guidance are also provided in Manual D Residential Duct Systems 2009 Edition published by the Air Conditioning Contractors of America.

    Metal ducts for residential HVAC systems are typically insulated on the exterior using a "duct wrap," such as fiberglass blanket insulation with a foil-faced vapor barrier.  Duct wrap comes in four-foot-wide rolls 50 to 100 feet long and in R-values that range from R-4 through R-8.  Before applying duct wrap, sheet metal duct should be clean, dry, and tightly sealed at all joints and seams. The 2009 IECC (Section 403.2) requires that supply ducts located in unconditioned space be insulated to at least R-8 (return ducts can be insulated to R-6). 

    Ducts should be sealed with duct mastic and/or metal tape that meets the requirements of the Underwriters Laboratory UL-181, UL-181A, or 181B (CEC 2005). Regular cloth-backed duct tape should not be used because it can dry out and fail quickly. Mastic is a thick, gooey, non-hardening substance that is spread onto the duct seams with a paintbrush or a putty knife. For additional strength with seams that are wider than 1/8 inch, cover the gap with fiberglass mesh tape then apply the mastic.

    How to Seal and Insulate Metal Duct

    1. Install the metal ducts. Fit pieces together at joints by sliding the wider pipe over the narrower connecting collars. Use screws to secure connections. Wipe ducts with a dry cloth to ensure they are clean and dry especially at all joints and seams.
    2. Use mastic to seal the seams along the lengths of the pipes, the seams in the elbows, the joints where the elbow and straight pieces are joined, where ducting is joined to the air handler, junctions between trunk ducts and branch ducts, and at duct boots.

      Seal all joints and seams in the metal ductwork with mastic before installing insulation.
      Figure 1. Seal all joints and seams in the metal ductwork with mastic, including all joints and seams in elbows, before installing insulation.
    3. Measure foil-faced blanket insulation to fit around the circumference of the pipe with two inches of overlap. Wrap the insulation around the duct with the facing to the outside so the 2-inch flap completely overlaps the facing and insulation at the other edge of the insulation. Insulation should be snugly butted but not wrapped too tightly, which would compress the insulation and reduce its R value. Follow the manufacturer’s "stretch-out" guidelines, which specify how much insulation to use, based on the pipe circumference, to ensure that the insulation thickness is maintained to achieve the rated R-value (see Table 1). The insulation should be a minimum of R-8 for all supply ducts and at least R-6 for all return ducts.
    Table 1 - Duct Insulation Stretch-Out Measurements
    Labeled Thickness (in.)Installed Compressed Thickness (in.)RoundSquareRectangular
    1.00.75P + 7.0"P + 6.0"P + 5.0"
    1.51.125P + 9.5"P + 8.0"P + 7.0"
    2.01.5P + 12.0"P + 10.0"P + 8.0"
    2.31.75P + 13.0"P + 11.0"P + 8.5"
    2.02.25P + 17.0"P + 14.5"P + 11.5"

    Stretch-outs include 2 inches (51 mm) for overlap.

    P = Perimeter of duct to be insulated

    1. Overlap the insulation and staple along the seam every 6 inches at the "tape flap" using outward-clinching staples.
    2. Wrap another piece of insulation around the next section of duct, overlapping two inches at the end of the first piece of insulation. Staple along the lengthwise seam and at the overlap. Continue overlapping and stapling until the entire length of duct is covered. After stapling, cover and seal all tape flaps and overlaps with UL-181 metal tape or mastic (mastic is recommended).
    3. Make sure insulation covers all pipe connections to trunk duct, junction boxes, and boots.
    When wrapping metal pipes with insulation, allow two inches of overlap and staple along the seam with outward clinching staples.
    Figure 2. When wrapping metal pipes with insulation, allow two inches of overlap and staple along the seam with outward clinching staples. Follow the insulation manufacturer’s guidelines for “stretch-out” to avoid pulling the insulation too tightly.

     

    Success
    Ensuring Success

    After ducts are installed and before drywall is installed, the duct system should be visually inspected by a HERS rater to ensure that all connections are properly fastened and sealed, preferably with mastic. Locations to inspect include the main supply trunk to branch connections, at the duct boots, duct splices, the return box to the return ducts, jump duct connections, and exhaust fan and ERV/HRV connections. HVAC ducts should be tested for air leakage and proper air flow with a duct blaster test. This test should be done before drywalling when any air leaks can still be accessed and sealed. Ducts should be insulated along the length including at connections and the insulation should not be compressed by tight strapping, by framing members, or by excessive bending. The insulation should be a minimum of R-8 for all supply ducts and at least R-6 for all return ducts.

    Climate
    Climate

    No climate specific information applies.

    Training
    Right and Wrong Images
    Image
    Trunk to duct connections are only mechanically fastened and not sealed
    Trunk to duct connections are only mechanically fastened and not sealed
    Image
    Trunk to duct connections are properly insulated and have been sealed with mastic
    Trunk to duct connections are properly insulated and have been sealed with mastic
    Image
    Duct work is uninsulated and not sealed at seams
    Duct work is uninsulated and not sealed at seams
    Image
    Seams are being properly sealed with mastic and mesh tape
    Seams are being properly sealed with mastic and mesh tape
    Image
    Boot is uninsulated
    Boot is uninsulated
    Image
    Duct insulation is installed over boot
    Duct insulation is installed over boot
    Image
    Insulation does not cover boot and is not sealed
    Insulation does not cover boot and is not sealed
    Image
    Right – Metal or fiberboard duct is mastic sealed at seams
    Right – Metal or fiberboard duct is mastic sealed at seams
    Image
    Right – Metal duct boot is properly sealed at seams
    Right – Metal duct boot is properly sealed at seams
    Image
    Right – Metal is mechanically fastened at junction
    Right – Metal is mechanically fastened at junction
    Image
    Right – Metal or fiberboard duct is mastic sealed at junction with duct register box
    Right – Metal or fiberboard duct is mastic sealed at junction with duct register box
    Image
    Wrong – This metal duct is crushed, is sealed with duct tape instead of mastic or UL-181 metal tape, and is not correctly supported.
    Wrong – This metal duct is crushed, is sealed with duct tape instead of mastic or UL-181 metal tape, and is not correctly supported.
    Image
    Right – The round metal ducts are sealed with mastic at all joints.
    Right – The round metal ducts are sealed with mastic at all joints.
    Image
    Right – This supply duct is thoroughly sealed at all joints with mastic to prevent air leakage and the duct is equipped with a damper to provide zoned heating and cooling along with other trunk ducts.
    Right – This supply duct is thoroughly sealed at all joints with mastic to prevent air leakage and the duct is equipped with a damper to provide zoned heating and cooling along with other trunk ducts.
    Image
    Right - Example of a small through-the-wall HRV duct unit; 1 of 14.
    Right - Example of a small through-the-wall HRV duct unit; 1 of 14.
    Image
    Right - Fan end view of a small through-the-wall HRV unit; 2 of 14.
    Right - Fan end view of a small through-the-wall HRV unit; 2 of 14.
    Image
    Right - Insulating sleeve for small through-the-wall HRV unit with sealing gasket; 3 of 14.
    Right - Insulating sleeve for small through-the-wall HRV unit with sealing gasket; 3 of 14.
    Image
    Right - Diameter measurement of small through-the-wall HRV unit; 4 of 14.
    Right - Diameter measurement of small through-the-wall HRV unit; 4 of 14.
    Image
    Right - A hole is drilled into the wall for installation small through-the-wall HRV; 5 of 14.
    Right - A hole is drilled into the wall for installation small through-the-wall HRV; 5 of 14.
    Image
    Right - A hand saw is used to remove wall material for a small through-the-wall HRV; 6 of 14.
    Right - A hand saw is used to remove wall material for a small through-the-wall HRV; 6 of 14.
    Image
    Right - A small through-the-wall HRV duct is installed in an exterior wall; 7 of 14.
    Right - A small through-the-wall HRV duct is installed in an exterior wall; 7 of 14.
    Image
    Right - Flaps are cut into house wrap installed over an HRV duct then taped out of the way to install flashing; 8 of 14.
    Right - Flaps are cut into house wrap installed over an HRV duct then taped out of the way to install flashing; 8 of 14.
    Image
    Right - An EPDM gasket is installed around an HRV duct installed in an exterior wall; 9 of 14.
    Right - An EPDM gasket is installed around an HRV duct installed in an exterior wall; 9 of 14.
    Image
    Right - After installing the EPDM gasket around the HRV duct, the lower edge of the gasket is taped first before taping the other edges of the gasket; 10 of 14.
    Right - After installing the EPDM gasket around the HRV duct, the lower edge of the gasket is taped first before taping the other edges of the gasket; 10 of 14.
    Image
    Right - After installing the EPDM gasket around the HRV duct, first the lower edge, then the sides of the gasket are taped; 11 of 14.
    Right - After installing the EPDM gasket around the HRV duct, first the lower edge, then the sides of the gasket are taped; 11 of 14.
    Image
    Right - After installing the EPDM gasket around the HRV duct, first the lower edge, then the sides, then the top of the gasket are taped; 12 of 14.
    Right - After installing the EPDM gasket around the HRV duct, first the lower edge, then the sides, then the top of the gasket are taped; 12 of 14.
    Image
    Right - House wrap is lapped back over first layer of flashing tape, then a second layer of flashing tape is applied to the sides around the duct; 13 of 14.
    Right - House wrap is lapped back over first layer of flashing tape, then a second layer of flashing tape is applied to the sides around the duct; 13 of 14.
    Image
    Right - A second layer of flashing tape is applied over the EPDM gasket and first layer of tape at sides and top around the duct; 14 of 14.
    Right - A second layer of flashing tape is applied over the EPDM gasket and first layer of tape at sides and top around the duct; 14 of 14.
    Image
    Wrong - The holes around the HRV ducting should be air sealed.
    Wrong - The holes around the HRV ducting should be air sealed.
    Compliance

    Compliance

    The Compliance tab contains both program and code information. Code language is excerpted and summarized below. For exact code language, refer to the applicable code, which may require purchase from the publisher. While we continually update our database, links may have changed since posting. Please contact our webmaster if you find broken links.

    Retrofit
    Existing Homes

    SCOPE

    Additions

    If new metal duct is added to an existing home, either as part of an addition or an equipment upgrade, ensure that the metal duct is installed in runs that are as short, straight, and direct as possible, and that they are well air sealed and insulated, as described in the Description tab.

    Existing Buildings

    In an existing building with metal duct and an under-performing HVAC system, inspect for lack of air sealing and adequate insulation. Symptoms may include poor comfort control and excessive energy use.

    For more information, view the U.S. Department of Energy’s Standard Work Specifications regarding ducts.

    If the ducts are located in the attic, review the guide Pre-Retrofit Site Assessment of Attics, Ceilings and Roofs.

    If the ducts are located in the basement or crawlspace, review the guide Pre-Retrofit Site Assessment of Crawlspaces and Basements.

    DESCRIPTION

    Uninsulated (or under-insulated) ducts waste heating and cooling energy when the ducts are located in unconditioned space.  In humid climates, they can also become a source of moisture damage. When warm, humid air comes in contact with the cold surface of a duct delivering chilled air the water vapor can condense to liquid water that can cause rust in the ducts and mold in insulation, framing, and other building materials.

    Air sealing and insulating is even important for ducts in conditioned space as these measures can help ensure hot or cold air reaches its destination.

    For the installation of sheet metal ducts in retrofit and existing building situations, follow all best practices and precautions in the Description tab for new construction. Poor comfort control and wasted energy occur when conditioned air doesn’t make it all the way to the target space (due to leakage in the system) or when the target temperature of the conditioned air is compromised (due to heat gain or loss through uninsulated or under-insulated ductwork.) Additionally, duct leakage can drive infiltration, increasing the entrance of uncontrolled outdoor air that requires conditioning.

    Note that the physical connections of all ducts must be properly sealed before the addition of insulation, and then the insulation material and jacketing must also be sealed. See Duct Sealing for detailed sealing guidance.

    Additions

    Coordinate the duct layout for a new space with the design of the structure and other systems to ensure there is space for proper routing. As with new construction, use ACCA Manual D and provide a drawing of the layout to the homeowner for future reference.  

    Existing Buildings

    See Pre-Retrofit Assessment of Existing HVAC Systems for a discussion of how to determine whether a flawed duct design may be contributing to poor HVAC system performance.

    ENSURING SUCCESS

    When re-routing ductwork, access the ducts directly from the basement, crawlspace, or attic if possible. If the ducts are behind finish materials like drywall, it is tempting to make the smallest possible openings in existing ceilings and walls in an effort to reduce disruption. It will be impossible to fully examine the entire duct layout if openings are too small. Instead, cut openings in drywall large enough to fit head and shoulders so that the duct can be manipulated into the best possible orientation.

    Although an existing duct system is generally not required to be brought up to code when making repairs (double check this with the local code official), you can take this opportunity to check the ducts for duct leakage and seal all accessible seams and joints; use outward-clinched staples and UL-181A-approved metal tape that is heat activated or pressure sensitive or use mastic and fiber mesh tape. You can also add duct insulation where it is lacking or deficient, especially if you see evidence that condensation has been occurring.

    Starting with the 2009 International Energy Conservation Code (IECC), supply ducts located in unconditioned space must be insulated to at least R-8, and return ducts must be insulated to R-6.

    COMPLIANCE 

    See Compliance tab. 

    More

    More Info.

    Access to some references may require purchase from the publisher. While we continually update our database, links may have changed since posting. Please contact our webmaster if you find broken links.

    References and Resources*
    Author(s)
    Aldrich Robb,
    Puttagunta Srikanth
    Organization(s)
    Consortium for Advanced Residential Buildings,
    CARB,
    National Renewable Energy Laboratory,
    NREL,
    Steven Winter Associates,
    SWA
    Publication Date
    Description
    Report describing the sealing and insulating of HVAC duct systems in existing homes.
    *For non-dated media, such as websites, the date listed is the date accessed.
    Contributors to this Guide

    The following authors and organizations contributed to the content in this Guide.

    Sales
    Building Science Measures
    Building Science-to-Sales Translator

    High-R Duct Insulation =

    Image(s)
    Technical Description

    Without adequate duct insulation, there can be significant heat loss or heat gain as conditioned air travels through the comfort delivery system. This is especially true where ducts are located in an uninsulated attic or crawlspace. Insulation significantly reduces this energy loss and helps ensure conditioned air is effectively distributed from the comfort equipment to a home’s living spaces.


    Sales Message
    Last Updated

    Did you find this information helpful?

    If you have questions and/or would like a reply to this feedback, please include your e-mail address in the message.
    This question is for testing whether or not you are a human visitor and to prevent automated spam submissions.