U.S. Department of Energy U.S. Department of Energy Energy Efficiency and Renewable Energy

Double Wall Framing

Please Register or Login to Provide Feedback.

Scope


Reduced Thermal Bridging

 

Double-Wall Framing*

  1. Install a continuous air barrier on the exterior of the interior wall.
  2. Seal all seams, gaps, and holes of the air barrier with caulk or foam.
  3. Install insulation without misalignments, compressions, gaps, or voids.  OR
  4. Completely fill entire cavity of the double wall assembly without misalignments, compressions, gaps, or voids.


*Only one item from 4.4.1 through 4.4.5 on the ENERGY STAR checklist must be installed to comply with ENERGY STAR.

Notes:

Up to 10% of the total exterior wall surface area is exempted from the reduced thermal bridging requirements to accommodate intentional designed details (e.g., architectural details such as thermal fins, wing walls, or masonry fireplaces; structural details, such as steel columns). It shall be apparent to the rater that the exempted areas are intentional designed details or the exempted area shall be documented in a plan provided by the builder, architect, designer, or engineer. The rater need not evaluate the necessity of the designed detail to qualify the home.

Mass walls utilized as the thermal mass component of a passive solar design (e.g., a Trombe wall) are exempt from this item. To be eligible for this exemption, the passive solar design shall be comprised of the following five components: an aperture or collector, an absorber, thermal mass, a distribution system, and a control system. For more information, visit the Energy Savers website.

 

Mass walls that are not part of a passive solar design (e.g., CMU block or log home enclosure) shall either utilize the strategies outlined in Item 4.4 (of the ENERGY STAR Thermal Enclosure System Rater Checklist). Or, the pathway in the assembly with the least thermal resistance, as determined using a method consistent with the 2009 ASHRAE Handbook of Fundamentals, shall provide ≥ 50% of the applicable assembly resistance, defined as the reciprocal of the mass wall equivalent U-factor in the 2009 IECC – Table 402.1.3. Documentation identifying the pathway with the least thermal resistance and its resistance value shall be collected by the rater and any Builder Verified or Rater Verified box under Item 4.4 (of the ENERGY STAR Thermal Enclosure System Rater Checklist) shall be checked.

Double-wall framing is defined as any framing method that ensures a continuous layer of insulation covering the studs to at least the R-value required in Item 4.4.1 (of the ENERGY STAR Thermal Enclosure System Rater Checklist), such as offset double-stud walls, aligned double-stud walls with continuous insulation between the adjacent stud faces, or single-stud walls with 2x2 or 2x3 cross-framing. In all cases, insulation shall fill the entire wall cavity from the interior to exterior sheathing except at windows, doors, and other penetrations.



Description


Double-wall construction is one option for high R-value walls. They are relatively inexpensive to construct and use readily available materials that construction crews may be more familiar with than other high-R-value options such as structural insulated panels (SIPS) and insulated concrete form (ICF) walls. Double-wall construction consists of two stud-framed walls set up next to each other to form an extra thick wall cavity that can be filled with insulation. Because the interior and exterior framing are separated by insulation, thermal bridging is also reduced or eliminated. Building Science Corporation, a Building America research partner, investigated several forms of double-wall construction including double-stud walls, truss walls, and offset frame walls in a study on high R-value walls (Straube and Smegal 2009). Some of the forms they investigated are described below.

Double walls would be designed and specified by the architect and implemented by the framers. Site supervisors should ensure that framers and trades responsible for air sealing, insulating walls, and installing windows are knowledgeable or trained in techniques required for double-wall construction and that skill level expectations are included in the contracts for these trades.

 

How to Construct a Double-Stud Wall with Cellulose Insulation

One form of double-wall construction consists of an exterior 2x6 or 2x4 stud-framed structural wall and a second 2x4 nonstructural wall built to the inside with a gap in between of several inches. If the studs in each wall are installed at the same spacing (e.g., 24-inch on-center) they can be staggered, although research has shown only minor improvement (<R-1) when staggering the studs (CARB 2009). Plywood boxes must be installed around the rough-in spaces for installing windows, which are typically installed flush with the exterior wall. The cladding attachment is the same as normal stud-framed construction practice.

The example shown here uses a 2x4 exterior structural wall built at 16-inches on-center and a second 2x3 wall built at 24-inches on-center that is nonstructural but is used to support drywall and electrical services. The two stud walls plus the gap in between provide a 9.5-inch cavity for cellulose insulation, which would have a clear-wall R-value (for that section of the wall without interruptions) of R-34 or a whole-wall R-value of R-30 (Straube and Smegal 2009). In this example, a Class I vapor barrier of 6-mil polyethylene is installed on the exterior side of the interior wall to control air leakage and vapor diffusion (see Straube and Smegal 2009 for more on moisture control). A vapor barrier may be appropriate in very cold climates, but is not necessary in warmer climates. If one is installed, it should be located as shown here on the exterior side of the interior wall and care should be taken that insulation on both sides of the vapor barrier is fully aligned with the barrier the entire length of the wall.

 

Double-stud wall with cellulose insulation

 

Figure 1 - This double-stud wall, consisting of a 2x4, 16-inch on-center exterior wall and a 2x3 24-inch on-center interior wall, provides 9.5 inches of wall cavity space filled with cellulose insulation for a whole wall R value of R-30 Reference

 

How to Construct a Double Stud Wall with Spray Foam

A combination of insulation types can be used. In this example, high-density spray foam provides increased air sealing and moisture protection, decreasing the risk of wintertime condensation on the interior side of the exterior wall while less expensive cellulose provides additional R-value. This example again uses a 2x4 exterior structural wall built at 16-inches on-center and an interior 2x3 nonstructural wall built at 24-inches on-center providing a 9.5-inch cavity. The exterior wall is covered with rigid fiberglass foam sheathing, and then the inside surface of the exterior wall is covered with 2 inches of high-density spray foam. For climate zones 6 and higher, a Class I vapor barrier of 6-mil polyethylene is installed on the back of the interior wall. (Class I vapor barriers are not recommended in warmer climates [See Straube and Smegal 2009 for more on moisture issues]). The cavities remaining in the interior wall and between the polyethylene and the spray foam are filled with a total of 7.5 inches of cellulose, for a calculated whole-wall R-value of R-32.4 and a clear-wall R-value of R-36.2 (Straube and Smegal 2009). 

 

Double-stud wall with spray foam and cellulose insulation

 

Figure 2 - This double-stud wall - consisting of a 2x4, 16-inch on-center exterior wall and a 2x3 24-inch on-center interior wall - has 2 inches of high-density spray foam applied to the interior surface of the exterior wall for air sealing and moisture control, plus 7.5 inches of cellulose insulation providing for a whole-wall R value of R-32.4 Reference

 

How to Construct a Truss Wall

The truss wall uses two sets of studs like the double-stud wall, but in this case the interior wall is the load-bearing wall. The exterior wall is attached at each stud and hangs cantilevered outside of the foundation wall, which frees up floor space compared to a traditional double-stud wall. The interior and exterior wall studs are aligned and connected with plywood gusset plates toward the top, middle, and bottom of each pair of studs, and a plywood cavity closure at the top and bottom of the stud cavities. These gussets and closures provide stability so that the walls can be further apart, allowing more room for insulation. The bottom edge of the exterior wall drops below the sill plate, providing space that can be filled with insulation along the exterior side of the rim joist, thus minimizing the thermal bridging that can otherwise occur through the rim joist.

In this example a 2x4, 16-inch on-center interior load-bearing wall is connected to a 2x3, 16-inch on-center exterior nonbearing wall spaced to provide 11 inches of cavity width that is filled with cellulose insulation for a calculated whole-wall R value of R-36.5 or clear-wall value of R-40.5 (Straube and Smegal 2009). This wall, which is designed for climate zones 6 or higher, has a Class I vapor barrier of 6-mil polyethylene installed between the interior wall and the drywall. (For warmer climate zones, no vapor barrier should be installed.) Because of the location of the plastic in this wall assembly immediately behind the drywall, it will be perforated by electrical wiring and plumbing. If the wall is not air sealed at the drywall layer, warm moist air could get into the wall cavity through these perforations and condense on cooler outer framing. (See Straube and Smegal 2009 for more on moisture issues).

 

Truss wall with cellulose insulation

 

Figure 3 - This truss wall - consisting of a 2x4, 16-inch on-center interior load-bearing wall connected to a 2x3, 16-inch on-center exterior nonbearing wall with plywood gussets - is spaced to provide 11 inches of cavity width that is filled with cellulose insulation for a calculated whole-wall R-value of R-36.5 or clear-wall value of R-40.5 Reference



Ensuring Success


An infrared camera used in conjunction with blower door testing may help indicate the thoroughness of insulation coverage and may also help detect air leakage through the wall, if a sufficient temperature difference exists between the outside and the conditioned space of the house. Insulation installation should be inspected by the site supervisor before drywall is installed.



Climate


No climate specific information applies.



Right and Wrong Images



Presentations

None Available



Videos

None Available




CAD Images




Compliance


ENERGY STAR Version 3, (Rev. 6)

Thermal Enclosure Checklist, Reduced Thermal Bridging. Reduced thermal bridging at above-grade walls separating conditioned from unconditioned space (rim / band joists exempted) using double-wall framing. Double-wall framing is defined as any framing method that ensures a continuous layer of insulation covering the studs to at least the R-value required in Item 4.4.1 of the Checklist, such as offset double-stud walls, aligned double-stud walls with continuous insulation between the adjacent stud faces, or single-stud walls with 2x2 or 2x3 cross-framing.  In all cases, insulation shall fill the entire wall cavity from the interior to the exterior sheathing except at windows, doors and other penetrations. Up to 10% of the total exterior wall surface area is exempted from the reduced thermal bridging requirements to accommodate intentional designed details (e.g., architectural details such as thermal fins, wing walls, or masonry fireplaces; structural details, such as steel columns.) Mass walls that are not part of a passive solar design (e.g., CMU block or log home enclosure) shall either utilize the strategies outlined in Item 4.4 or the pathway in the assembly with the least thermal resistance as determined using a method consistent with the 2009 ASHRAE Handbook of Fundamentals, shall provide 50% of the applicable assembly resistance, defined as the reciprocal of the mass wall equivalent U-factor in the 2009 IECC – Table 402.1.3. Documentation verifying the pathway with the least thermal resistance and its resistance value shall be collected by the rater and any builder verified or rater verified box under Item 4.4 shall be checked. Mass walls utilized as the thermal mass component of a passive solar design (e.g., a Trombe wall) are exempt from this item. To be eligible for this exemption, the passive solar design shall be comprised of the following five components:  an aperture or collector, an absorber, thermal mass, a distribution system, and a control system.

 

DOE Challenge Home

Exhibit 1: Mandatory Requirements. Certified under ENERGY STAR Qualified Homes Version 3. Ceiling, wall, floor, and slab insulation shall meet or exceed 2012 IECC levels and achieve Grade 1 installation, per RESNET standards.

 

2009 IECC

This topic is not specifically addressed in the 2009 IECC.

 

2009 IRC

This topic is not specifically addressed in the 2009 IRC.

 

2012 IECC

This topic is not specifically addressed in the 2012 IECC.

 

2012 IRC

This topic is not specifically addressed in the 2012 IRC.



Case Studies

None Available


References

  1. 2009 IECC—International Energy Conservation Code

    2009 IECC, International Energy Conservation Code. International Code Council, Washington, D.C.

  2. 2012 IECC—International Energy Conservation Code

    2012 IECC, International Energy Conservation Code.  International Code Council, Washington, D.C.

  3. All About Larsen Trusses

    Holladay, M. 2011. All About Larsen Trusses. Green Building Advisor, Newtown, Connecticut.

  4. Building America Special Research Project: High-R Walls Case Study Analysis

    Straube, J. and J. Smegal. 2009. Building America Special Research Project: High-R Walls Case Study Analysis. RR-0903. Prepared by the Building Science Corporation for the Department of Energy, Building America Program.

  5. DOE Challenge Home National Program Requirements

    DOE. 2012. DOE Challenge Home National Program Requirements (Rev. 02). Office of Energy Efficiency and Renewable Energy, U.S. Department of Energy, Washington, D.C.

  6. Double Wall: Staggered or In-Line Studs?

    Consortium for Advanced Residential Buildings (CARB). 2009. Double Wall: Staggered or In-Line Studs? Prepared by the Consortium for Advanced Residential Buildings for the U.S. Department of Energy, Building America Program.

  7. ENERGY STAR Qualified Homes, Version 3 (Rev. 06) Inspection Checklist for National Program Requirements

    EPA. 2012. ENERGY STAR Qualified Homes, Version 3 (Rev. 06) Inspection Checklist for National Program Requirements. U.S. Environmental Protection Agency, Washington, D.C.

  8. High R-Value Wall Assembly-04: Double Stud Wall Construction

    Building Science Corporation. 2009. High R-Value Wall Assembly-04: Double Stud Wall Construction. Building Science Corporation.

  9. How to Install Cellulose Insulation

    Holladay, M. 2011. How to Install Cellulose Insulation. Green Building Advisor, Newtown, Connecticut.

  10. Thermal Enclosure System Rater Checklist Guidebook

    EPA. 2011. Thermal Enclosure System Rater Checklist Guidebook. U.S. Environmental Protection Agency, Washington, D.C.